CITY OF COLLEGE STATION
MEMORANDUM
November 14, 2007
TO: Veronica Morgan, Mitchell & Morgan, LLP, via v(cr�mitchellandmorgan.com
FROM: Jason Schubert, Staff Planner
SUBJECT: CSISD CREEK VIEW ELEMENTRAY (SP)- Site Plan
Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff
review comments detailing items that need to be addressed. Please address the comments
and submit the following information for further staff review:
One (1) complete set of construction documents for the proposed development
with the revised site and landscaping plans attached
One (1) revised site plan
One (1) landscaping plan
Easement Dedication Sheet and required documents (please allow 4 weeks to
process)
Other engineering documents as detailed in the comments.
Please note that the Easement Dedication Sheet and necessary documents are required prior
to the issuance of a building permit. If there are comments that you are not addressing with the
revised site plan, please attach a letter explaining the details. If you have any questions or need
additional information, please call me at 979.764.3570.
Attachments: Staff review comments
pc: Mike Ball, College Station ISD, via mballna csisd.orq
Case file #07-00500282
NOTE: Any changes made to the plans, that have not been requested by the City of College Station,must be explained in your next transmittal
letter and"bubbled"on your plans. Any additional changes on these plans that have not been pointed out to the City,will constitute a
completely new review. Page 1 of 3
STAFF REVIEW COMMENTS NO. 1
Project: CSISD CREEK VIEW ELEMENTRAY (SP) — 07-00500282
PLANNING
1. Since rezoning is not considered for ISD projects, please remove the proposed zoning line
and references to proposed zoning.
2. Provide easement dedication sheet for the proposed ROW dedication for Eagle Avenue.
3. Please note the address for the site is 1001 Eagle Avenue.
4. It appears the "Future Portable Building Location" does not have adequate fire coverage. If it
is to remain on this site plan as a proposed building location, fire coverage needs to be
provided. If the location is removed and portable structures are proposed in the future, a
revised site plan, meeting fire coverage, will need to be submitted at that time.
5. Please provide a Landscape Plan for review. While the Landscape Plan will not be
reviewed for compliance with Unified Development Ordinance 7.5 (Landscaping and Tree
Protection), it will be checked for conflicts with proposed utilities and infrastructure.
6. Please note that 100% coverage of groundcover, decorative paving, decorative rock, or a
perennial grass is required in parking lot islands, swales and drainage areas, the parking lot
setback, rights-of-way, and adjacent property disturbed during construction.
7. Please note that if an irrigation system is installed, it will need to be tested prior to issuance
of a Certificate of Occupancy as per the following general notes: Irrigation system must be
protected by either a Pressure Vacuum Breaker, a Reduced Pressure Principle Back Flow
Device, or a Double-Check Back Flow Device, and installed as per City Ordinance 2394 and
All BackFlow devices must be installed and tested upon installation as per City Ordinance
2394.
Reviewed by: Jason Schubert Date: November 14, 2007
ENGINEERING COMMENTS NO. 1
1. Provide Drainage Report.
2. Provide Water Design Report.
3. Provide Sewer Design Report.
4. Our GIS floodplain does not appear to match you on the ground topography. Determine
location of floodplain on the ground. What is BFE?
5. Show all proposed public utility easements and provide easement dedication
documentation.
6. Please review general construction notes on Sheet C01. A number of the notes need to
be updated with current information.
7. The FIRM panel listed on Sheet CO1 is not the most current there is a "D" issue.
8. Please designate sanitary sewer line as private.
9. Indicate TCEQ crossing requirements for water and sewer.
10. The water line profile is labeled Storm Sewer "F" (Sheet CO3). Also, the sheet title does
not include water line. Is it supposed to be on this sheet?
11. Please review TCEQ requirements for waterlines crossing intermittent streams. Provide
valves and encasement as required.
12. Show conflict with proposed sanitary sewer line. (Sheet CO3)
13. Please re-label Fireline as Fire Suppression Line.
14. In order to eliminate the dead end fire hydrant line (Waterline C), please relocate the 8"
line in front of the building to the rear, providing a looped system.
NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmittal
letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a
completely new review. Page 2 of 3
15. It is preferred that you cross over the 36" storm pipe if you can keep 3 feet of cover.
(Waterline A)
16. Remove the 4" waterline lead at the 45 bend (Waterline B). It appears that this will need
to be a metered connection at the time it is needed.
17. Additional comments may result when required reports are submitted and reviewed.
Reviewed by: Carol Cotter Date: November 13, 2007
ELECTRICAL COMMENTS REQUIRING IMMEDIATE ATTENTION
1. Developer provides temporary blanket easement for construction purposes.
2. Developer provides easements for electric infrastructure as installed for electric lines
(including street lights).
GENERAL ELECTRICAL COMMENTS
1. Developer installs conduit per City specs and design.
2. City will provide drawings for conduit installation.
3. Developer provides 30' of rigid or IMC conduit for each riser pole. City installs riser.
4. Developer to intercept existing conduit at designated transformers, pole or device and
extend as required.
5. If conduit does not exist at designated transformer, pole or device developer will furnish and
install conduit as shown on electrical layout.
6. Developer pours transformer and/or device pad(s) per City specs and design.
7. Developer installs pull boxes and secondary pedestals as per City specs and design (pull
boxes and secondary pedestals provided by the City).
8. Developer provides digital AutoCAD 2000 or later version of plat and/or site plan. Email to:
gmartinez@cstx.gov.
9. Developer provides load data for project as soon as it becomes available so that
transformers can be sized and ordered and material can be allocated.
10. To discuss any of the above electrical comments please contact Gilbert Martinez at
979.764.6255.
Reviewed by: Gilbert Martinez Date: November 7, 2007
FIRE
1. Will there be overhangs or covered walkways? (Bus pickup and drop off), aerial ladder
concerns.
Reviewed by: Steve Smith Date: November 7, 2007
SANITATION
1. Need to show garbage dumpster pad and enclosure.
Reviewed by: Wally Urrutia Date: November 9, 2007
NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmittal
letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a
completely new review. Page 3 of 3
1 1101 Texas Avenue, P.O. Box 9960
College Station,Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
CITY OF COLLEGE STATION
MEMORANDUM
January 8, 2008
TO: Veronica Morgan, Mitchell & Morgan, LLP, via vmitchellandmorqan.com
FROM: Jason Schubert, Staff Planner
SUBJECT: CSISD CREEK VIEW ELEMENTRAY (SP) - Site Plan
Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff
review comments detailing items that need to be addressed. Please address the comments
and submit the following information for further staff review:
Seven (7) complete sets of construction documents for the proposed
development with the revised site attached (one set will be returned to you,
please submit additional copies if you want more than one approved set)
Two (2) revised site plans
One (1) 11x17 grading and erosion control plan
If there are comments that you are not addressing with the revised site plan, please attach a
letter explaining the details. If you have any questions or need additional information, please
call me at 764-3570.
Attachments: Staff review comments
cc: Mike Ball, College Station ISD, via mballcsisd.org
Jon Hall, College Station ISD, via jhall(a�csisd.orq
Steve Aloway, VLK Architects, via aloway(a�vlkarchitects.com
Case file #07-00500282
STAFF REVIEW COMMENTS NO. 2
Project: CSISD CREEK VIEW ELEMENTRAY (SP) - 07-00500282
PLANNING
1. No further comments.
Reviewed by: Jason Schubert Date: December 3, 2007
ENGINEERING COMMENTS NO. 2
1. Once Eagle Avenue is constructed you will need to relocate construction exit to school
property. How will you ensure construction traffic does not use Newport Lane?
2. Relocate the Dove Crossing construction exit to CSISD property.
3. Provide flushing mechanism for low point(s) in water line.
4. Fire flow report states velocities are at or below 12 fps, but report shows velocities above 12
fps in 2 sections of line. However, this will be allowed since this is preferable to increasing
the line size.
5. Water line encasement should extend into high bank. Refer to BCS Unified Design
Guidelines for requirements.
6. Show connection of Eagle Avenue to existing roadway. Plans just show "end of roadway".
7. Clearly indicate that only storm sewer associated with and in Eagle Avenue ROW is public.
The rest will be maintained by CSISD.
8. Junction box required at all changes in alignment. Manholes to be provided at intervals not
less than 300 feet. Storm Sewer "F".
9. Drainage Report Certification cites "The Lofts".
10. What is the study point location for Exhibits 8-11?
11. Include BCS Unified Detail Sheets.
Reviewed by: Carol Cotter Date: January 4, 2008
MITCHELL
MM
MORGAN
January 8, 2008
Jason Schubert
City of College Station
Planning& Development Services
PO Box 9960
College Station, TX 77842
RE: STAFF REVIEW COMMENTS NO. 2
CSISD CREEK VIEW ELEMENTARY(SP)- 07-00500282
Dear Jason,
Attached are the following items for the CSISD Creek View Elementary site plan:
• One (1) complete set of construction documents for the proposed
development with the revised site attached for Carol Cotters review. If all
is okay an additional thirteen (13) full sets from VLK will be sent to the
City for stamping.
• Two (2)revised site plans
• One (1) 11x17 grading and erosion control plan
STAFF REVIEW COMMENTS NO.2
PLANNING
It is acknowledged that no comments were made, however if this changes please do not
hesitate to call(979) 260-6963.
ENGINEERING COMMENTS NO. 2
1. Once Eagle Avenue is constructed you will need to relocate construction exit to
school property. How will you ensure construction traffic does not use Newport
Lane?
RESPONSE: We have noted on sheet 2 that the construction exit will be moved to the
school property once Eagle Avenue has been constructed. We have also noted on
that same sheet that no construction traffic shall use Newport Lane and the
contractor shall maintain barricades at Newport until construction of Eagle Avenue
and the school is complete.
2. Relocate the Dove Crossing construction exit to CSISD property.
RESPONSE: This construction exit has been relocated to CSISD property on sheet 2.
3. Provide flushing mechanism for low point(s) in water line.
RESPONSE:A blow-off assembly has been added to sheet C3.
511 UNIVERSITY DRIVE EAST,SUITE 204 • COLLEGE STATION,TX 77840 • T 979.260.6963 • F 979.260.3564
CIVIL ENGINEERING • HYDRAULICS • HYDROLOGY • UTILITIES • STREETS • SITE PLANS • SUBDIVISIONS
info@mitchellandmorgan.com • www.mitchellandmorgan.com
4. Fire flow report states velocities are at or below 12 fps, but report shows velocities
above 12 fps, in 2 sections of line. However, this will be allowed since this is
preferable to increasing the line size.
RESPONSE: Understood.
5. Water line encasement should extend into high bank. Refer to BCS Unified Design
Guidelines for requirements.
RESPONSE: The waterline encasement has been lengthened as shown on sheet 3.
6. Show connection of Eagle Avenue to existing roadway. Plans just show "end of
roadway".
RESPONSE: This connection detail has been added to sheet C3 and a note added to the
contractor at the existing Eagle terminus referring to this detail.
7. Clearly indicate that only storm sewer associated with and in Eagle Avenue ROW is
public. The rest will be maintained by CSISD.
RESPONSE: The section of private storm sewer has been labeled on sheet 3.
8. Junction box required at all changed in alignment. Manholes to be provided.at
intervals not less than 300 feet. Storm Sewer"F".
RESPONSE:A junction box has been added to storm sewer "F".
9. Drainage Report Certification cites"The Lofts".
RESPONSE:A new certification sheet was submitted to Carol Cotter on 1/7/08.
10. What is the study point location for Exhibits 8-11?
RESPONSE:A new exhibit is attached which shows these study points.
11. Include BCS Unified Detail Sheets.
RESPONSE: These detail sheets are already included in the overall plan set for
Creekview Elementary school and these plans for Eagle Avenue are part of that
overall set.
If you have any further questions please do not hesitate to call (979) 260-6963.
' cerely,
1
Veronica 1 rg. IP. •.
Managing Partne
CC: Jon Hall, College Station, ISD,via ihall@csisd.org
Steve Aloway, VLK Architects,via aloway(a vlkarchitects.com
File