HomeMy WebLinkAboutStaff Review STAFF REVIEW COMMENTS NO. 2
Project:AUTUMN CHASE REPLAY(FP)-06-00500184
PLANNING
1. Per staff review comment #2 of the first round review dated August 28th.'Please check the lot area for the
proposed lots. It appears that several are not meeting the minimum 3500 square foot per dwelling unit. Identify lot area on
each lot." Lot 2A of Block 4 still is not meeting the 3,500-square foot in area required in Section 5.2
Residential Dimensional Standards. The Ordinance allows for lot width reduction for duplex lots if you
are providing off-street parking in the rear or side yard. The lot area requirement of 3,500 square feet is
still required.
If the minimum lot area cannot be met, the plat cannot proceed to the Planning and Zoning
Commission. Either the lot lines need to be shifted to meet the minimum lot area requirement or a
variance request application will need to be filled out and submitted for the Zoning Board of
Adjustments.
2. (FYI) Please make sure that you are working with Sanitation on this project for trash pick up. (Wally
Urrrutia Sanitation Superintendent- 764-3841)
Reviewed by:Jennifer Reeves Date: September 6, 2006
NOTE: Any changes made to the plans,that haze not been requested by the City of College Station,must be explained in your next transmittal letter and`bubbled"on
your plans.Any additional changes on these plans that haze not been pointed out to the City,will constitute a completely new renew
2 of 2
STAFF REVIEW COMMENTS NO. 1
Project:AUTUMN CHASE (FP) - 06-00500184
PLANNING/ENGINEERING
1. Lots 1A, 1B & 2A of Block 4 and Lot 4A of Block3 are not meeting the minimum lot width
requirements per Section 5.2 residential Standards for Duplex construction in an R-6 zoning
district (60-feet w/parking in the rear or side yard).
2. Please check the lot area for the proposed lots as well. It appears that several are not meeting the
minimum 3500 square foot per dwelling unit. Identify lot area on each lot.
3. Please adjust the plat to meet the above referenced comments or submit a revised application
with variance request for the requirements that are not being met.
4. Provide coordinates,lengths and bearing on all curves (Per Sven Griffin GIS).
Reviewed by:Jennifer Reeves/Carol Cotter Date:August 24,2006
GENERAL ELECTRICAL COMMENTS
1. Developer installs conduit per city specs and design.
2. City will provide drawings for conduit installation.
3. Developer to intercept existing conduit at designated transformers and extend as required.
4. If conduit does not exist at designated transformer, developer to furnish and install conduit
as shown on electrical layout.
5. Developer installs secondary pedestals as per city specs and design.(secondary pedestals
provided by the city).
6. Developer provides digital AutoCAD 2000 or later version of plat and/or site plan email to
sweido(a,cstx.gov
7. To discuss any of the above electrical comments,please contact Sam Weido at 979.764.6314.
Reviewed by: Sam Weido Date: 8-23-06
NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained
in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not
been pointed out to the City,will constitute a completely new review. 2