CITY OF COLLEGE STATION
Planning d•Development Services
1101 Texas Avenue,P.O. Box 9960
College Station,Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
MEMORANDUM
April 21,2006
TO: David Schuler- Spirit Custom Homes Via fax 690.2256
FROM: Jennifer Reeves,Project Manager
SUBJECT: AUTUMN CHASE FOURPLEXES LOT 7 & 8 (SP) - Site Plan
Staff reviewed the above-mentioned site plan as requested. The following page is a list of staff review
comments detailing items that need to be addressed. The next submittal will be the third and final review by
staff for this round of reviews. If all items have not been addressed on the next submittal, another $200
processing fee will need to be submitted for the subsequent set of three (3) reviews. Please address the
comments and submit the following information for further staff review:
One (1) landscaping plan
If there are comments that you are not addressing with the revised site plan,please attach a letter explaining
the details. If you have any questions or need additional information,please call me at 764-3570.
Attachments: Staff review comments
cc: Veronica Morgan - Mitchell & Morgan, LLP Via fax 260.3564
Case file#06-00500068
rii nle Ul texas tkocin Universlly
TRANSMISSION VERIFICATION REPORT
TIME : 04/20/2006 00: 19
NAME : COCS DEVELOPMENT SER
FAX : 9797643496
TEL : 9797643570
SER.# : BROE2J341073
DATE,TIME 04/20 00:19
FAX NO./NAME 96902256
DURATION 00:00:28
PAGE(S) 02
RESULT OK
MODE STANDARD
ECM
°"x41111M1IFEti CITY OF COLLEGE STATION �mlNgatli 't>n
lllgtrl3!1,irk m+inNK..
9 fi ,ri �'Il,sr1' nsr ySarrjm PMrrnlrlli.
II31M�sMHnnimnrmTm.r„r. rn .r . ,.....,. .,,...,.,._....... ................ �--._ ^• '•w•^ +"` +rn.rmmrrn.a,.ml+�iwn
11.01 Texas Avenue, P.O.Box 9960
College Station,Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
MEMORANDUM
April 21,2006
TO: David Schuler- Spirit Custom homes Via tax 690.2256
FROM: Jennifer Ree-e ,Prof ect MAnager
SUBJECT: AUTUMN CHASE FOURPLEXES LOT 7 & 8(SP) - Site Plan
114111.1
Staff reviewed the above-mentioned site plan as reclu.estecl. The following page is a list of staff review
comments detailing items that need to be addressed. The next submittal will be the third and final review by
staff for, this round of. reviews. If all items have not been addressed on the next submittal, another $200
processing fee will need to be submitted for the subsequent set of three (3) reviews. Please address the
comments and submit the following information for further staff review:
One (1) landscaping plan
If there are comments that you are not addressing with the revised site plan,please attach a letter explaining
the details. If you have any questions or need additional information,please call.me at 764-3570.
ALLadLtn iLs. Staff review comments
CITY OF COLLEGE STATION
Planning&Development Services
1101 Texas Avenue, P.O. Box 9960
College Station, Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
MEMORANDUM
April 11, 2006
TO: David Schuler - Spirit Custom Homes Via fax 690.2256
FROM: Jennifer Reeves, Project Manager
SUBJECT: AUTUMN CHASE FOURPLEXES- Site Plan
Staff reviewed the above-mentioned site plan as requested. The following page is a list
of staff review comments detailing items that need to be addressed. Please address the
comments and submit the following information for further staff review:
One (1) complete set of construction documents for the proposed
development with the revised site and landscaping plans attached (please
submit additional copies to be stamped for your records)
One (1) 11x17 grading and erosion control plan
Easement Dedication Sheet and required documents (please allow 4
weeks to process).
Please note that the Easement Dedication Sheet and the necessary documents are
required prior to the issuance of a building permit. If there are comments that you are not
addressing with the revised site plan, please attach a letter explaining the details. If you
have any questions or need additional information, please call me at 979.764.3570.
Attachments: Staff review comments
cc: Veronica Morgan - Mitchell & Morgan, LLP Via fax 260.3564
Case file #06-00500068
TRANSMISSION VERIFICATION REPORT
TIME : 04/10/2006 13: 13
NAME : COCS DEVELOPMENT SER
FAX : 9797643496
TEL : 9797643570
SER. # : BROE2J341073
DATE,TIME 04/10 13: 12
FAX NO. /NAME 96902256
DLIRATION 00: 00: 54
PAGES) 03
RESULT OK
MODE STANDARD
ECM
CITY OF COLLEGE STATION
Plctnni,tg&Develnpmrnt Smilers
/101 Texas Avenue, P.O. Box 9960
College Station, Texas 77842
Phone 97 9.764.3570 / Fax 979.764.3496
MEMORANDUM
April 11, 2006
TO: David Schuler Spirit Custom Homes Via fax 690.2256
FROM: Jennifer Reeves, Project Manager
SUBJECT: AUTUMN CHASE FOURPLEXES- Site Plan
Staff reviewed the above-mentioned site plan as regiipsted. The following page is a list
of staff review comments detailing items that need to be addressed, Please address the
comments and submit the following information for further staff review:
One (1) complete set of construction documents for the proposed
development with the rcvisod site and landscaping plans attached (please
submit additional copies to be stamped for your records)
One (1) 11x17 grading and erosion control plan
Easement Dedication Sheet and required documents (please allow 4
TRANSMISSION VERIFICATION REPORT
TIME : 04/10/200E 13: 15
NAME : COCS DEVELOPMENT SEP
FAX : 9797643496
TEL : 9797643570
SER. # : BROE2J341073
DATE,TIME 04/10 13:14
FAX NO. /NAME 92603564
DURATION 00:00: 49
PAGE(S) 03
RESULT OK
MODE STANDARD
ECM
411,11111111
CITY OF COLLEGE STATION
Planning er Development Services
1101 T'c us Av rtue, F.O. 13ux 9960
College Station, Texas 77842
Phone 979.764.3570 / Fax 979.764.3496
MEMORANDUM
April 11, 2006
TO: David Schuler- Spirit Custom Homes Via fax 690.2256
FROM: Jennifer Reeves, Project Manager
SUBJECT: AUTUMN CHASE FOURPLEXES- Site Plan
Staff reviewed the above-mentioned site plan as requested. The following page is a list
of staff review comments detailing items that need to be addressed. Please address the
comments and submit the following information for further staff review:
One (1) complete set of construction documents for the proposed
development with the revised site and landscaping plans attached (please
submit additional copies to be stamped for your records)
One (1) 11x17 grading and erosion control plan
Easement Dedication Sheet and required documents (please allow 4
wooks to nroccssl.
—
002 'U‘4
MITCHELL
MM �o,a6
MORGAN t4
April 5, 2006
Carol Cotter, EIT
Development Services
P.O. Box 9960
College Station, TX 77840
RE: Autumn Chase Fourplexes Fireflow
Dear Carol:
The Autumn Chase Fourplexes follow the assumptions as stated in the Autumn Chase
Subdivision Fire Flow Analysis Addendum dated May 16, 2005. The fourplexes are
separated with firewalls constructed per building code between units, with the greatest
area between walls of 1634 square feet. As stated in the Autumn Chase Fire Flow Analysis
Addendum, the fireflow required by the 2000 International Building Code is 1500 gpm.
Hydrants and lines constructed with the Autumn Chase Subdivision are sufficient for the
fire flow requirements of the fourplexes project. Please see the Autumn Chase Subdivision
Fire Flow Analysis Addendum for further calculations.
Sincerely,
111!
Veronica J.B. i ior..'n, , CFM
Managing Partner
cc. David Schuler
S:\Proj\0549-Schuler_A.0._4Plexes-lot-7and8\docs\0549-fireflow.doc
511 UNIVERSITY DRIVE EAST,SUITE 204 • COLLEGE STATION,TX 77840 • T.979.260.6963• F. 979.260.3564
CIVIL ENGINEERING • HYDRAULICS • HYDROLOGY • UTILITIES • STREETS • SITE PLANS • SUBDIVISIONS
info@mitchellandmorgan.com • www.mitchellandmorgan.com
,
MITCHELL &
MM 1N°1
5
MORGAN (tYVY
April 5, 2006
Carol Cotter, EIT
Development Services
P.O. Box 9960
College Station, TX 77840
RE: Autumn Chase Fourplexes Fireflow-Lots 1 &2
Dear Carol:
The Autumn Chase Fourplexes follow the assumptions as stated in the Autumn Chase
Subdivision Fire Flow Analysis Addendum dated May 16, 2005. The fourplexes are
separated with firewalls constructed per building code between units, with the greatest
area between walls of approximately 1500 square feet. As stated in the Autumn Chase Fire
Flow Analysis Addendum, the fireflow required by the 2000 International Building Code is
1500 gpm. Hydrants and lines constructed with the Autumn Chase Subdivision are
sufficient for the fire flow requirements of this fourplexes project. Please see the Autumn
Cha e Subdivision Fire Flow Analysis Addendum for further calculations.
Si :rely,
/ )11
i die Li---
Veronica J.B. Morgan, PE, CFM
Managing Partner
cc. David Schuler
S:\Proj\0619-shuler-4plexes-lot-1and2\docs\0619-fireflow.doc &UPI- (.6
O ea VI tOrttAb
—b lie,`
644-eaJ 4 PiAJhu-?,,,,,-,
511 UNIVERSITY DRIVE EAST,SUITE 204 • COLLEGE STATION,TX 77840 • T.979.260.6963 • F.979.260.3564
CIVIL ENGINEERING • HYDRAULICS • HYDROLOGY • UTILITIES • STREETS • SITE PLANS • SUBDIVISIONS
info@mitchellandmorgan.com • www.mitchellandmorgan.com
L-VOQ
April 11, 2006
City of College Station
Planning & Development Services
P.O. Box 9960
College Station, TX 77842
Attn: Jennifer Reeves
Re: Autumn Chase Fourplexes (SP)
Dear Jennifer,
Attached with this letter please find the following:
• One (1) complete set of construction documents for the proposed
development with the revised site and landscaping plans attached
• One (1) 11x17 grading and erosions control plan
• Easement Dedication Sheet
Below are the answers the City Staff Review comments on April 11, 2006.
PLANNING
Comment:/Provide a general note that all roof and ground-mounted
mechanical equipment shall be screened from view or isolated so
as not to be visible from any public right-of-way or residential
district within 150' of the subject lot, measured from a point five feet
above grade. Such screening shall be coordinated with the building
architecture and scale to maintain a unified appearance.
Answer: Note is added to the plans.
Comment:✓ Please provide a parking legend on the site plan showing required
parking and provided parking.
Answer: See parking legend on plan.
Comment:'The patio located on the north end of the building #8 is located in a
utility easement. Please be aware that this patio will not be
permitted to have an awning or cover of any type.
Answer: Acknowledged.
Comment. Please provide a shared parking and access easement.
Answer: </Please
basement documents are forthcoming.
Comment: provide a blanket easement or actual PUE dedication for
meter relocation.
Answer: See attached blanket easement.
MISCELLANE9L1S
Comment./ Irrigation system must be protected by either a Pressure Vacuum
Breaker, a Reduced Pressure Principle Back Flow Device, or a
Double-Check Back Flow Device, and installed as per City
Ordinance 2394.
Answer: Acknowledged on irrigation plan
Comment: backflow backflow devices must be installed and tested upon installation
as per City Ordinance 2394.
Answer: Acknowledged
Comment: Please provide an erosion control plan.
Answer: See attached.
LANDSCAPIN9ISTREETSCAPING/BUFFER
Comment:,/ Provide a general note that 100% coverage of groundcover,
decorative paving, decorative rock, or a perennial grass is required
in parking lot islands, swales and drainage areas, the parking lot
setback, rights-of-way, and adjacent property disturbed during
construction.
Answer: Corrected plan with complete sod on above listed items.
Comment/Per Section 7.5 Landscape and Tree Protection in the Unified
Development Ordinance and per the Site Plan checklist please
provide a landscape legend providing total site area, Point
calculations, total points required, total points provided. Please
provide a caliper of trees.
Answer: /See corrected landscape plans.
Comment:JPlease be aware that every project must expand a minimum of 50%
of its point total on canopy trees.
Answer: (Acknowledged
Comment:.) Non-canopy trees accumulate 40 points with at least 4-14.5 inch
caliper. Currently the landscape plan is showing 75 points a piece.
According to the City of College Station approved plan list "Myrica.
Cerfiera-Wax myrtle" is listed as a shrub not a non-canopy
species. This will not be an acceptable non-canopy tree. (Please
see City of College Station Approved Plant List).
Answer: ( Acknowledged
Comment:) Please note on the landscape plan that an irrigation plan is required
to be submitted, reviewed, approved and installed prior to
Certificate of Occupancy.
Answer: Note irrigation plan on separate page.
Comment Parking is required to be screened from view of the right-of-way.
Please screen parking spaces 14-20 and 21&22 from Autumn
Chase Loop. Please be aware that screening shrubs are required
to be 3-feet in height at planting stage. A dwarf species is not
permitted for screening (Please see City of College Station
Approved Plant List)
Answer: Acknowledged on new landscape plan.