HomeMy WebLinkAboutstaff review STAFF REVIEW COMMENTS NO. 5 Project: CULPEPPER (DOMINION) REPLAT (FP) - 06-00500066 PLANNING 1. Please resubmit the Plat without the signature block for the City Secretary. Response to the last review comments stated that it was removed but was not resubmitted. 2. Sheet CO1.1 - The legend is incorrect. Lots 2-A and 2-B seemed to be mixed up as well as Lots 2-E and 2-F. Lot 2-H does not match what you reflected in the legend. 3. Again, staff will go on record at the Planning and Zoning Commission meeting that we will not be supporting the building setback variances that are to be requested from the Zoning Board of Adjustments. 4. The construction documents and reports are still under review and may affect the plat. Reviewed by: Jennifer Reeves Date: January 19, 2007 STAFF REVIEW COMMENTS NO. 3 Project: CULPEPPER (DOMINION) REPLA.T (FP) -06-00500066 PLANNING 1. Due to the odd shaped lots, please identify the lot lines for each lot with a different color or different line types and provide a legend. Perhaps some of these questions can be answered with a 1"=10' scale. 2. Dumpster enclosures are required to be 12' x 12' and for two dumpsters the requirement is 12' x 24'.Please provide the correct size enclosure. 3. Please provide a curb and pavement detail. 4. Staff will not support a plat that is creating lots that cannot meet the required building setbacks. 5. Please remove the City Secretary's signature from the Planning and Zoning Commission certification. 6. (FYI) Lots 2-J thru 2-F Facing George Bush will be required a front setback, not a side street setback.The same goes fot Lots 2-A thru 2-D that face Puryear Drive. 7. (FYI) A private access easement is being shown at Domixiik Drive. A driveway cut will not be permitted at this location. Reviewed by:Jennifer Reeves Date:January 8, 2007 STAFF REVIEW COMMENTS NO. 3 Project: CULPEPPER (DOMINION) REPLAT (FP) - 06-00500066 PLANNING 1. Due to the odd shaped lots, please identify the lot lines for each lot with a different color or different line types and provide a legend. Perhaps some of these questions can be answered with a 1"=10' scale. 2. Dumpster enclosures are required to be 12' x 12' and for two dumpsters the requirement is 12' x 24'. Please provide the correct size enclosure. 3. Please provide a curb and pavement detail. 4. Staff will not support a plat that is creating lots that cannot meet the required building setbacks. 5. Please remove the City Secretary's signature from the Planning and Zoning Commission certification. 6. (FYI) Lots 2-J thru 2-F Facing George Bush will be required a front setback, not a side street setback. The same goes for Lots 2-A thru 2-D that face Puryear Drive. 7. (FYI) A private access easement is being shown at Dominik Drive. A driveway cut will not be permitted at this location. Reviewed by:Jennifer Reeves Date:January 8, 2007 STAFF REVIEW COMMENTS NO. 3 Project: CULPEPPER (DOMINION) REPLAT (FP) - 06-00500066 PLANNING 1. The driveway variance must go before the Design Review Board and decided before the plat can proceed,as the location of the access easement does not comply with City Ordinances. 2. Lots 2-A, 2-B, 2-C & 2-D are divided up by the driveway which would be considered as duplex lots. R-3 Zoning District is one of a group of no less than three, nor more than twelve, attached dwelling units. The R-3 Zoning District does not allow for duplex development. 3. A drainage and access easement is being shown off of Dominik. An access easement will not be permitted off of Dominik. 4. It appears from looking at the building placement on the construction documents that the required building setbacks are not going to be feasible, therefore staff cannot not support this plat. 5. The construction documents and reports are still under review and may affect the plat. Reviewed by:Jennifer Reeves Date: November 13, 2006 NOTE: Any changes made to the plans, that have not been requested by the City of College Station,must be explained in your next transmittal letter and"bubbled"on your plans. Any additional changes on these plans that have not been pointed out to the City,will constitute a 2of2 completely new review. 0 August 21, 2006 Gessner Engineering City of College Station Development Services Department 1101 Texas Avenue College Station, Texas 77840 Re: Dominion on Dominik Culpepper Plaza Replat (FP) — Final Plat (06-00500066) GE Job No.: 06-0120 Dear Sirs: Attached is the revised Final Plat for the proposed Dominion on Dominik project located at the intersection of George Bush East, Dominik and Puryear Drives. The revised Final Plat was prepared based upon the comments received from the Staff Review Comments No. 1 dated July 31 and August 1, 2006. Responses to each comment are provided in the body of this letter and in the order presented. Planning /1. The building areas were removed from the plat /2. All lots except the common area are 2,000 square feet in size. /3. The County of Dallas Certificate was removed from the Plat. /4. The City Council approval was removed from the Plat. / 5. Each Lot Number has been reassigned as requested.cA six foot wide sidewalk will be provided along Dominik and Puryear ives as requested. 7. The construction plans for the extention of utilities to the site are attached. /8. I contacted Wally in Sanitation and he indicated that we will be able to use two (2), 300 gallon dumpsters for solid waste disposal. 1712 Southwest Parkway,Suite#105,College Station,Texas 77840•P.O.Box 10763,77842-0763•979.680.8840•FAX 979.680.8841 1400 South Austin Street,Brenham,Texas 77833•979.836.6855•FAX 979.836.6847 www.GessnerEngineering.eom Engineering 1. The detention facilities shall not be situated within the Public utility easements. 2. Proposed public utility easements have been added between the lots as depicted on the Final Plat. 3. Construction documents associated with the extension of public utilities to this site are provided for your review. I have also attached the engineer's cost estimate for the extension of these public utilities. 4. The proposed location of the private water and sanitary sewer services are denoted on the construction documents for the City of College Station Staff review. 5. The construction documents for the extension of the public utility services are attached for your review as requested. Electrical 1. The developer shall install the requested conduits per the specs and design. 2. The developer understands that the City will provide drawings for conduit installation. 3. The developer shall provide 30 feet of rigid or IMC conduit for riser poles. 4. The developer shall intercept the existing conduit at the designated transformer and extend as required. 5. The developer shall furnish and install conduit as shown on the electrical layout if it does not exist. 6. The developer shall pour the transformer pads as per the City of College Station specifications and design. 7. The developer shall install pull boxes and secondary pedestals as per the City of College Station specifications and design. Gessner Engineering 8. The developer shall provide digital AutoCAD 2000 or later version of the Final Plat to wdavis(ci to civ when approved. 9. The developer shall provide the load data for the project with the electrical plans. 10. The developer shall provide a temporary blanket easement with the construction plan submitted for review. 11. The developer shall provide electric easements for electrical infrastructure as installed for electric lines (including street lights). It has been a pleasure to submit this information to the Development Services department. If you have any questions, please contact me. Sincerely, Gessner Engineering IMF Alto 'ogers, P.E. Gessner Engineering ENGINEERING COMMENTS NO. 2 (Clarification for previous comments NO. 1) 1. Private drainage facilities or detention ponds should not be located in public utility easements. 2. Public Utility Easements are only desired where public utilities are being extended or need to be extended in the future. 3. Construction documents are required for the needed extensions of public water and sanitary sewer mains. Each lot should be adjacent to both water and sanitary sewer mains. Water main extensions should be looped. 4. Please provide the proposed locations for the private water and sanitary sewer service lines from the main to each lot on the previously mentioned construction documents. Private service lines are not allowed to cross adjacent lots. 5. The submittal and review of these construction documents are a requirement of this final plat being forwarded to P&Z. Reviewed by: Josh Norton Date: August 1, 2006 ENGINEERING COMMENTS NO. 1 1. Please submit construction documents for require public water and sanitary sewer infrastructure extensions. 2. Please differentiate public utility easements from private drainage easements, as it has not been the practice of the CoCS to maintain private detention ponds or private drainage easements. Reviewed by: Josh Norton Date: July 28, 2006 STAFF REVIEW COMMENTS NO. 1 Project: CULPEPPER PLAZA REPLAT (FP) - 06-00500066 PLANNING 1. The construction documents and reports are still under review and may affect the plat. Reviewed by:Jennifer Reeves Date:August 25, 2006 NOTE: Any changes made to the plans,that haze not been requested by the City of College Station,must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that haze not been pointed out to the City,will constitute a completely new review 2of2 ENGINEERING COMMENTS NO. 2 (Clarification for previous comments NO. 1) 1. Private drainage facilities or detention ponds should not be located in public utility easements. 2. Public Utility Easements are only desired where public utilities are being extended or need to be extended in the future. 3. Construction documents are required for the needed extensions of public water and sanitary sewer mains. Each lot should be adjacent to both water and sanitary sewer mains. Water main extensions should be looped. 4. Please provide the proposed locations for the private water and sanitary sewer service lines from the main to each lot on the previously mentioned construction documents. Private service lines are not allowed to cross adjacent lots. 5. The submittal and review of these construction documents are a requirement of this final plat being forwarded to P&Z. Reviewed by: Josh Norton Date: August 1, 2006 STAFF REVIEW COMMENTS NO. 1 Project: CULPEPPER PLAZA REPLAT (FP) - 06-00500066 PLANNING L\ 1. Please remove the building area depicted on the plat. Only lot lines need to be shown. 2. Minimum lot area for R-3 is 2000-square feet. Lot is not meeting this area requirement, thus a variance will be required. The variance request will have to go before the Zoning Board of Adjustments prior to the Plat moving forward to the Planning and Zoning Commission. 3. Please remove the County of Dallas Certificate off of the Plat. The subject property is located in Brazos County. 4. Please remove the Approval of City Council Certificate off of the Plat. This certificate is not required. 5. Please assign each lot a lot number or a letter and block for identification. (Example: Lotl-R, Block A) 6. A 6-foot sidewalk will be required along Puryear Street and the existing side walk along George Bush East will need to be finished out with this development. 7. The construction documents and reports are still under review and may affect the plat.. 8. This project will not be required a site plan, how will trash pick up be handled? (Please contact Wally in Sanitation @ 764.3841) Reviewed by:Jennifer Reeves Date:July 25,2006 ENGINEERING COMMENTS NO. 1 1. Please submit construction documents for require public water and sanitary sewer infrastructure extensions. 2. Please differentiate public utility easements from private drainage easements, as it has not been the practice of the CoCS to maintain private detention ponds or private drainage easements. Reviewed by: Josh Norton Date: July 28, 2006 ELECTRICAL 1. Developer installs conduit per city specs and design. 2. City will provide drawings for conduit installation. 3. Developer provides 30' of rigid or IMC conduit for riser poles. City installs riser. 4. Developer to intercept existing conduit at designated transformers and extend as required. 5. If conduit does not exist at designated transformer, developer to furnish and install conduit as shown on electrical layout. 6. Developer pours transformer pad(s) per city specs and design. 7. Developer installs pull boxes & secondary pedestals as per city specs and design. (pull boxes & secondary pedestals provided by the city). NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. 2 8. Developer provides digital AutoCAD 2000 or later version of plat and/or site plan email to wdavis@cstx.gov 9. Developer provides load data for project. 10. Developer provides temporary blanket easement for construction purposes. 11. Developer provides easements for electric infrastructure as installed for electric lines (including street lights). 12. To discuss any of the above electrical comments, please contact Weldon Davis at 979.764.5027. Reviewed by: Weldon Davis Date: July 25, 2006 NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. 3 STAFF REVIEW COMMENTS NO. 5 Project: CULPEPPER(DOMINION) REPLAT(FP)-06-00500066 PLANNING 1. Please resubmit the Plat without the signature block for the City Secretary. Response to the last review comments stated that it was removed but was not resubmitted. 2. Sheet CO1.1 - The legend is incorrect. Lots 2-A and 2-B seemed to be mixed up as well as Lots 2-E and 2-F. Lot 2-1-i does not match what you reflected in the legend. 3. Again, staff will go on record at the Planning and Zoning Commission meeting that we will not be supporting the building setback variances that are to be requested from the Zoning Board of Adjustments. 4. The construction documents and reports are still under review and may affect the plat. Reviewed by: Jennifer Reeves Date: January 19, 2007 STAFF REVIEW COMMENTS NO. 1 Project: CULPEPPER PLAZA REPLAT(FP) -06-00500066 PLANNING 1. Please remove the building area depicted on the plat. Only lot lines need to be shown. 2. Minimum lot area for R-3 is 2000-square feet. Lot is not meeting this area requirement, thus a variance will be required. The variance request will have to go before the Zoning Board of Adjustments prior to the Plat moving forward to the Planning and Zoning Commission. 3. Please remove the County of Dallas Certificate off of the Plat. The subject property is located in Brazos County. 4. Please remove the Approval of City Council Certificate off of the Plat. This certificate is not required. 5. Please assign each lot a lot number or a letter and block for identification. (Example: Lotl-R, Block A) 6. A 6-foot sidewalk will be required along Puryear Street and the existing side walk along George Bush East will need to be finished out with this development. 7. The construction documents and reports are still under review and may affect the plat.. 8. This project will not be required a site plan, how will trash pick up be handled? (Please contact Wally in Sanitation @ 764.3841) Reviewed by:Jennifer Reeves Date:July 25,2006 ENGINEERING COMMENTS NO. 1 1. Please submit construction documents for require public water and sanitary sewer infrastructure extensions. 2. Please differentiate public utility easements from private drainage easements, as it has not been the practice of the CoCS to maintain private detention ponds or private drainage easements. Reviewed by: Josh Norton Date: July 28, 2006 ELECTRICAL 1. Developer installs conduit per city specs and design. 2. City will provide drawings for conduit installation. 3. Developer provides 30' of rigid or IMC conduit for riser poles. City installs riser. 4. Developer to intercept existing conduit at designated transformers and extend as required. 5. If conduit does not exist at designated transformer, developer to furnish and install conduit as shown on electrical layout. 6. Developer pours transformer pad(s) per city specs and design. 7. Developer installs pull boxes & secondary pedestals as per city specs and design. (pull boxes & secondary pedestals provided by the city). NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. 2 8. Developer provides digital AutoCAD 2000 or later version of plat and/or site plan email to wdavis@cstx.gov 9. Developer provides load data for project. 10. Developer provides temporary blanket easement for construction purposes. 11. Developer provides easements for electric infrastructure as installed for electric lines (including street lights). 12. To discuss any of the above electrical comments, please contact Weldon Davis at 979.764.5027. Reviewed by: Weldon Davis Date: July 25, 2006 NOTE: Any changes made to the plans,that have not been requested by the City of College Station,must be explained in your next transmittal letter and"bubbled"on your plans.Any additional changes on these plans that have not been pointed out to the City,will constitute a completely new review. 3 ENGINEERING COMMENTS NO. 2 (Clarification for previous comments NO. 1) 1. Private drainage facilities or detention ponds should not be located in public utility easements. 2. Public Utility Easements are only desired where public utilities are being extended or need to be extended in the future. 3. Construction documents are required for the needed extensions of public water and sanitary sewer mains. Each lot should be adjacent to both water and sanitary sewer mains. Water main extensions should be looped. 4. Please provide the proposed locations for the private water and sanitary sewer service lines from the main to each lot on the previously mentioned construction documents. Private service lines are not allowed to cross adjacent lots. 5. The submittal and review of these construction documents are a requirement of this final plat being forwarded to P&Z. Reviewed by: Josh Norton Date: August 1, 2006