HomeMy WebLinkAboutFire Flow Report P.O.Box 9253,College Station,TX 77$42 MEOff/Fax: (979)690-0329 C.orisu/-rt E ine-ers email.civil@rmengineer.corn February 15,2008 Josh Norton,E.I.T. Graduate Engineer City of College Station 1101 Texas Avenue South College Station,TX 77842 RE: Fire Flow Report for A&M Super Storage @ Wellborn 4000 Greens Prairie Road West,College Station, TX RME No.213-0304 Josh Norton: A fire flow test was performed in accordance with National Fire Prevention Association (NFPA) Standard 291, Chapter 4, for the above referenced project, on February 15, 2008. The results of this test are shown on the attached data sheet, and are sufficient to meet the City of College Stationminimum design standards for fire flow requirements. Please call should you have any questions. Sincerely, .4,`, . ff?. t te dew vow IN Rabon A.Metcalf, P.E., 88583 ration Ce neer.com Irk�1' ,C 0.4.%,0000, �SSi�IUAL SN« NNZIvize4.7 Maw Adam J. Bru baugh, E.I.T. adam@rmengineer.com CD 1-213-0304-L IS Page I of 1 FIRE FLOW TEST REPORT Date February 15, 2008 Location A&M Super Storage at Wellborn Flow Hydrant#1 Desc. j-ik/ )1,71.1167--Gr (ZNG- . or A*m skipEre s72,12466-; ter.9,. &Oc C A.. Nozzle size 2.5 Pitot Reading 5 GPM 12.50 Flow Hydrant#2 Desc. rr1-). ^' ' 1ti Th of -71-i .- 5atnNtaE57" eORA/F.R D! A *m St.Pg2 577)(06, Lor 1., I'ac K.L. Nozzle size 2.5 Pitot Reading 5 GPM 1250 Static Hydrant Desc. ` i m57 1 aG N-Yb2AAIT / 5i4.176(2 6,3 /N&S GT. Static PSI (oto Residual PSI (05 COMMENTS: ( E,br /sS 5 ittoikf MR. F-4610 ,NYpRAhAIT3 4, STArk, 1-1 ybIAN-r .S /VWA( A l-zoE WERE TAK J As riot.) /4}4j2dykriS 0 1.. #2. ti)EiZe: PZZoc<.7/t16 Ar 1716 S-,4in£ 77076 Al ' i -r// 1 -sA_fir 2 /.5 Zoc -- Signature, le Date O& _ 'Z//5/20,3 Signature, itle Date '1"---- RME Consulting Engineers POST OFFICE BOX 9253 COLLEGE STATION,TEXAS 77842 OFF/FAX: (979)690-0329 Co` "lti"1 E Ing ers E-mail: civil@rmengineer.com P.O.Box 9253,College Station,TX 77842 MEOff/Fax:(979)690-0329 --.r Consu/ti 5 Engineers email: civil@rmengineer.com November 19,2007 Development Services City of College Station 1101 Texas Avenue South College Station,TX 77842 RE: A&M Super Storage @ Wellborn—Acknowledgement of City Standards College Station E.T.d.,Brazos County,TX RME No.213-0304 To Whom It May Concern: The purpose of this letter is to acknowledge that the construction plans for the water line improvements,for the above referenced project,to the best of my knowledge do not deviate from the latest B/CS Design Guideline Manual except were specified below. 1. Gate valves and boxes are not shown to be installed along the main line (16" water line) at the two tees for the two fire hydrants. Only the branch line, at these two tees,is shown to have gate valves. This deviation to the B/CS DGM is per the direction and approval of Mr.Stephen Cast,manager of the Wellborn S.U.D. I also acknowledge, to the best of my knowledge that the details provided in the construction plans are in accordance with the B/CS Standard Details. Please do not hesitate to call if you have any questions. Sincerely, lE OF T0000; �1� ••. I •. t) .44 0, RA N A. ETCALF p RabonA.Mete. f P.E. •••• ••• •• ••••••••� rabon@rmengineer.com • epf �'•3 a.'k�d� •ii�v St'•••4'+/✓ CD1-213-0304-L10 Page l of 1 P.O.Box 9253,College Station,TX 77842 MEOff/Fax: (979) 690-0329 C.onSuttitly EnyineerS email:civil@rmengineer.com November 7,2007 Josh Norton, E.I.T. Graduate Engineer City of College Station 1101 Texas Avenue South College Station,TX 77842 RE: Fire Flow Analysis for A&M Super Storage @ Wellborn—Revision No. 1 4000 Greens Prairie Road West,College Station,TX RME No. 213-0304 Josh Norton: There is sufficient capacity in the existing water distribution system to support the above referenced development. This development's water line improvements were integrated into the KYPIPE hydraulic model, generated by this office, for the modeling efforts of the master planned community of Creek Meadows. This hydraulic model is attached and contains pipe distribution modeling within the Wellborn SUD system from Royder Road to Wellborn Oaks and from Greens Prairie Road West to Greens Prairie Trail which will also include the District's elevated storage tank. The existing and proposed improvements, and requirements, for fire flows are summarized below: ❖ The subject property has accessibility to existing public water for both domestic and fire use at the following locations: o Existing 16" PVC public water line located in an existing 16' PUE, along the right-of-way line of Greens Prairie Road West will be relocated (approximately 200 linear feet) into a new 20' PUE required for the dedication of ROW along Greens Prairie Road West. This relocated water line is called P-60 in the KYPIPE hydraulic analysis; o The proposed/relocated 16" PVC public water line will accommodate fire flows to two (2) new fire hydrants set within the property These two hydrants are labeled FH-101 and FH-102 in the KYPIPE model; o Fire hydrant FH-101 will be installed at the end of a new 8" PVC public water line. This new water line is called P-62 in the KYPIPE hydraulic analysis; o Flow tests were obtained from the Wellborn S.UD. from a fire hydrant was installed along the 12" PVC water line that is located on the east side of Greens CD1-213-0304-L09 Page 1 of 3 0 (CY)033 l—o4°t -o7 c? :SS Ac A&M Super Storage @ Wellborn MEFire Flow Analysis-Revision No.1 ,,,,Consul-tiny Engineers November 7,2007 Prairie Trail. Since the time of the original flow test the fire hydrant has been removed and an 8" waterline extension has been installed. This flow test was conducted on December 28, 2006 by Wellborn S.U.D. by Mr. Steven Cast and witnessed by this office. The flow data is summarized below in Table #1 —Flow Test Data. TABLE#1 FLOW TEST DATA Flow Pilot Static Fire Static Residual Hydrant Reading Flow Hydrant Pressure Pressure No. Location (psi) (gpm) No. (psi) (psi) FH"A" Greens Prairie Trail 67 1360 Res. 74 70 Note: The reported flow is from the 2.5"nozzle of the identified flow hydrant; ❖ Fire Flow requirements and results: o Commercial fire hydrants will be analyzed to provide a fire flow of 2,500 gpm. This flow may be split between two hydrant so long as they are within 600' of one another; o During fire flow conditions,the proposed system and adjacent infrastructure must provide the required fire flow with a minimum residual pressure of 20 psi; o At all analyzed conditions, no water line shall have a velocity greater than 12 fps in both existing and proposed mains; o Utilizing the KYP1PE model, mentioned above, fire flow requirements for the proposed water system improvements were determined to adequately meet or positively exceed the minimum design standards. Resulting summary information for the fire flow scenario is illustrated below in Table #2 — Water System Summary and identifies the"worse-case" location in the water distribution system (lowest pressure node or highest velocity in pipe). The entire water system model is fully contained with the KYPIPE Hydraulic Analysis Data. TABLE#2 WATER SYSTEM SUMMARY PIPE DATE NODE DATA Residual Fire Flow KYPIPE Pipe Size Flow Velocity Node Pressure Scenerio Name (in) (gpm) (fps) Name (psi) FIRE FLOW CONDITIONS 1 P-62 1 8 1250.00 7.98 I F-101 I 62.31 CD1-213-0304-L09 Page 2 of 3 A&M Super Storage @ Wellborn MEFire Flow Analysis-Revision No.1 >,axGonsutrincr Engineer's November 7,2007 , Fire Flow Scenario: o 1,250 gpm from FH-101 &FH-102; Please call should you have any questions or require assistance. Sincerely, =s9 to; OF F '- •ee• �. .r.•.• V. METC AL • lj 0 ' 5.3 Rabon A. Metcalf, P ,:?:;••,•A o ��' rabon@rmengineer.coa • A •'���/� NG® CD1-213-0304-L09 Page 3 of 3 * * * * * * * * * * K Y P I P E 4 * * * * * * * * * * * * * University of Kentucky Network Modeling Software * * * Copyrighted by KYPIPE LLC * * Version 3 - 11/01/2005 * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * Date & Time: Wed Nov 07 07:14:48 2007 INPUT DATA FILENAME C:\Users\user\RME\Projects\213-03-1\ENGINE-1\0304W1RB.DT2 TABULATED OUTPUT FILENAME C:\Users\user\RME\Projects\213-03-1\ENGINE-1\0304W1RB.OT2 POSTPROCESSOR RESULTS FILENAME C:\Users\user\RME\Projects\213-03-1\ENGINE-1\0304W1RB.RS2 ************************************************ SUMMARY OF ORIGINAL DATA ************************************************ UNITS SPECIFIED FLOWRATE = gallons/minute HEAD (HGL) = feet PRESSURE = psig PIPELINE DATA STATUS CODE: XX -CLOSED PIPE CV -CHECK VALVE P IPE NODE NAMES LENGTH DIAMETER ROUGHNESS MINOR N AME #1 #2 (ft) (in) COEFF. LOSS COEFF. P-1 R-1 J-1 500.00 16.00 139.4518 0.74 P-10 FH-1 J-4 291.00 8.00 139.4518 0.00 P-11 J-7 J-8 162.00 3.00 139.0000 0.00 P-12 J-5 J-9 308.00 6.00 139.0000 6.00 P-13 J-9 FH-2 108.00 6.00 139.4518 0.74 P-14 FH-2 FH-4 812.00 6.00 139.4518 1.31 P-15 FH-4 J-3 291.00 8.00 139.4518 0.00 P-16 J-6 J-11 1670.00 16.00 139.4518 0.00 P-17 J-11 1-12 1320.00 12.00 139.4518 0.74 P-18 J-12 J-13 459.00 8.00 139.4518 1.14 P-19 J-13 FH-7 126.00 8.00 139.4518 6.00 P-2 J-1 J-35 200.00 16.00 139.4518 3.57 2-20 J-13 FH-16 338.00 8.00 139.4518 3.57 2-21 J-14 J-10 146.00 3.00 139.0000 0.00 2-22 J-14 FH-5 68.00 8.00 139.4518 0.40 2-23 FH-5 FH-14 216.00 8.00 139.4518 0.74 P-24 FH-14 J-16 141.00 8.00 139.4518 0.74 P-25 J-16 FH-6 157.00 8.00 139.4518 0.00 P-26 FH-14 J-17 261.00 3.00 139.0000 0.00 2-27 J-16 J-18 304.00 3.00 139.0000 0.00 P-28 FH-7 FH-15 400.00 8.00 139.4518 0.74 P-29 FH-15 FH-8 247.00 6.00 139.4518 0.74 2-3 J-3 J-2 195.00 16.00 139.4518 0.74 2-30 FH-8 J-20 176.00 6.00 139.4518 0.00 P-31 FH-15 J-21 328.00 6.00 139.4518 0.74 P-32 J-21 3-22 219.00 3.00 139.0000 0.00 2-33 J-21 FH-9 205.00 6.00 139.4518 0.00 2-34 FH-9 FH-13 541.00 8.00 139.4518 9.91 2-35 FH-13 J-23 382.00 8.00 139.4518 6.74 2-36 FH-13 FH-10 602.00 8.00 139.4518 9.74 2-37 FH-10 J-25 136.00 3.00 139.0000 0.00 P-38 FH-10 FH-11 341.00 8.00 139.4518 0.74 P-39 FH-11 3-26 267.00 3.00 139.0000 0.00 p-4 J-3 J-4 294.00 16.00 139.4518 0.74 P-40 FH-11 FH-12 443.00 8.00 139.4518 0.00 P-41 FH-12 J-28 145.00 3.00 139.0000 0.00 P-42 J-23 3-1 2842.00 4.00 139.0000 0.00 P-43 J-12 J-27 1933.00 12.00 139.0000 0.00 P-44 J-27 3-23 1640.00 4.00 139.0000 0.00 P-45 J-11 R-2 500.00 16.00 139.4518 0.00 P-46 FH-16 3-14 336.00 8.00 139.4518 0.00 P-47 FH-11 FH-1A 175.00 8.00 139.0000 0.74 P-48 FH-1A 3-15 245.00 3.00 139.0000 0.74 P-49 FH-1A J-19 322.00 6.00 139.0000 0.74 P-5 J-4 3-6 1207.00 16.00 139.4518 2.24 P-50 J-19 J-24 104.00 3.00 139.0000 0.00 P-51 3-19 FH-2A 399.00 6.00 139.0000 0.17 P-52 FH-1A FH-3A 473.00 8.00 139.0000 0.17 P-53 FH-3A J-29 379.00 3.00 139.0000 0.74 P-54 FH-3A 3-30 112.00 8.00 139.0000 0.57 P-55 FH-3A J-31 387.00 6.00 139.0000 0.00 P-56 3-31 FH-2A 197.20 6.00 139.0000 0.74 P-57 3-31 FH-4A 387.87 6.00 139.0000 1.14 P-58 FH-4A J-32 99.00 8.00 139.0000 0.00 P-59 FH-4A 3-34 275.00 8.00 139.0000 0.74 P-6 J-6 J-5 118.00 6.00 139.4518 0.91 Ulla, N6111:4 ��N P-60 J-35 FH-102 200.00 16.00 139.4518 1.14 P-61 FH-102 3-2 1400.00 16.00 139.4518 0.00 �, ��M P-62 J-35 F-101 200.00 8.00 125.0000 0.57 P-7 J-5 FH-3 151.00 8.00 139.4518 0.40 P-8 FH-3 3-7 412.00 8.00 139.4518 0.74 P-9 J-7 FH-1 228.00 8.00 139.4518 0.40 END NODE DATA NODE NODE EXTERNAL JUNCTION EXTERNAL NAME TITLE DEMAND ELEVATION GRADE (gPm) (ft) (ft) F-101 F-101 1250.00 345.00 41000SO ea FH-1 0.00 333.00 FH-10 0.00 308.00 FH-102 FH-102 1250.00 343.0 0 �� WT S FH-11 0.00 313.00 FH-12 0.00 313.00 FH-13 16.50 305.00 FH-14 0.00 315.00 FH-15 13.50 306.00 FH-16 0.00 307.00 FH-1A 0.00 316.00 FH-2 0.00 333.00 FH-2A 21.00 316.00 FH-3 0.00 326.00 FH-3A 0.00 320.00 FH-4 0.00 333.00 FH-4A 0.00 318.00 FH-5 0.00 313.00 FH-6 0.00 316.00 FH-7 0.00 309.00 FH-8 0.00 303.00 FH-9 0.00 307.00 J-1 0.00 342.00 J-2 0.00 340.00 J-3 6.00 339.00 J-4 10.50 339.00 J-5 16.50 327.00 J-6 0.00 328.00 J-7 7.50 330.00 J-8 6.00 329.00 J-9 21.00 323.00 J-10 10.50 312.00 J-11 0.00 311.00 J-12 0.00 305.00 J-13 0.00 307.00 J-14 12.00 314.00 J-15 15.00 318.00 J-16 4.50 315.00 J-17 10.50 314.00 J-18 13.50 313.00 J-19 15.00 313.00 J-20 7.50 302.00 J-21 18.00 309.00 J-22 12.00 310.00 J-23 0.00 305.00 J-24 4.50 312.00 J-25 6.00 304.00 J-26 18.00 309.00 J-27 0.00 295.00 J-28 36.00 311.00 J-29 22.50 322.00 J-30 0.00 322.00 J-31 28.50 318.00 J-32 3.00 320.00 J-34 0.00 318.00 J-35 J-35 0.00 343.00 R-1 Wellborn Ele ---- 342.00 497.00 R-2 Flow Test ---- 311.00 497.00 O UTPUT OPTION DATA OUTPUT SELECTION: ALL RESULTS ARE INCLUDED IN THE TABULATED OUTPUT S YSTEM CONFIGURATION NUMBER OF PIPES (p) = 62 NUMBER OF END NODES (j) = 56 NUMBER OF PRIMARY LOOPS (1) = 5 NUMBER OF SUPPLY NODES (f) = 2 NUMBER OF SUPPLY ZONES (z) = 1 Case: 0 RESULTS OBTAINED AFTER 8 TRIALS: ACCURACY = 0.00000 S IMULATION DESCRIPTION (LABEL) M.D.W. Centre - Phase One P IPELINE RESULTS STATUS CODE: XX -CLOSED PIPE CV -CHECK VALVE P IPE NODE NUMBERS FLOWRATE HEAD MINOR LINE HL+ML/ HL/ N AME #1 #2 LOSS LOSS VELO. 1000 1000 (gpm) (ft) (ft) (ft/s) (ft/ft) (ft/ft) P-i R-1 3-1 1820.47 0.83 0.10 2.90 1.86 1.66 P-10 FH-1 3-4 54.92 0.02 0.00 0.35 0.07 0.07 P-11 J-7 J-8 6.00 0.02 0.00 0.27 0.15 0.15 2-12 3-5 3-9 49.54 0.08 0.03 0.56 0.35 0.25 2-13 3-9 FH-2 28.54 0.01 0.00 0.32 0.10 0.09 P-14 FH-2 FH-4 28.54 0.07 0.00 0.32 0.09 0.09 2-15 FH-4 J-3 28.54 0.01 0.00 0.18 0.02 0.02 2-16 3-11 3-6 773.88 0.57 0.00 1.23 0.34 0.34 2-17 J-11 3-12 261.15 0.24 0.01 0.74 0.19 0.19 2-18 3-12 3-13 220.81 0.45 0.04 1.41 1.05 0.98 2-19 3-13 FH-7 169.81 0.08 0.11 1.08 1.47 0.60 P-2 3-1 J-35 1793.62 0.32 0.45 2.86 3.89 1.62 P-20 J-13 FH-16 51.00 0.02 0.01 0.33 0.08 0.06 P-21 3-14 3-10 10.50 0.06 0.00 0.48 0.41 0.41 2-22 J-14 FH-5 28.50 0.00 0.00 0.18 0.03 0.02 P-23 FH-5 FH-14 28.50 0.00 0.00 0.18 0.02 0.02 P-24 FH-14 J-16 18.00 0.00 0.00 0.11 0.01 0.01 P-25 3-16 FH-6 0.00 0.00 0.00 0.00 0.00 0.00 2-26 FH-14 J-17 10.50 0.11 0.00 0.48 0.41 0.41 P-27 J-16 3-18 13.50 0.20 0.00 0.61 0.66 0.66 P-28 FH-7 FH-15 169.81 0.24 0.01 1.08 0.64 0.60 2-29 FH-15 FH-8 7.50 0.00 0.00 0.09 0.01 0.01 P-3 J-3 J-2 706.38 0.06 0.01 1.13 0.36 0.29 P-30 FH-8 3-20 7.50 0.00 0.00 0.09 0.01 0.01 2-31 FH-15 J-21 148.81 0.63 0.03 1.69 2.01 1.91 2-32 J-21 3-22 12.00 0.12 0.00 0.54 0.53 0.53 2-33 J-21 FH-9 118.81 0.26 0.00 1.35 1.26 1.26 2-34 FH-9 FH-13 118.81 0.17 0.09 0.76 0.47 0.31 P-35 3-23 FH-13 67.19 0.04 0.02 0.43 0.16 0.11 P-36 FH-13 FH-10 169.50 0.36 0.18 1.08 0.89 0.60 P-37 FH-10 J-25 6.00 0.02 0.00 0.27 0.15 0.15 P-38 FH-10 FH-11 163.50 0.19 0.01 1.04 0.60 0.56 P-39 FH-11 J-26 18.00 0.30 0.00 0.82 1.12 1.12 2-4 J-4 J-3 683.84 0.08 0.01 1.09 0.32 0.27 2-40 FH-11 FH-12 36.00 0.02 0.00 0.23 0.03 0.03 2-41 FH-12 3-28 36.00 0.59 0.00 1.63 4.06 4.06 2-42 3-1 J-23 26.85 1.65 0.00 0.69 0.58 0.58 2-43 J-12 3-27 40.34 0.01 0.00 0.11 0.01 0.01 2-44 J-27 3-23 40.34 2.03 0.00 1.03 1.24 1.24 P-45 R-2 J-11 1035.03 0.29 0.00 1.65 0.58 0.58 2-46 FH-16 J-14 51.00 0.02 0.00 0.33 0.06 0.06 P-47 FH-11 FH-1A 109.50 0.05 0.01 0.70 0.30 0.27 2-48 FH-1A J-15 15.00 0.20 0.01 0.68 0.82 0.80 P-49 FH-1A 3-19 40.25 0.05 0.00 0.46 0.18 0.17 2-5 3-6 3-4 639.42 0.29 0.04 1.02 0.27 0.24 P-50 3-19 J-24 4.50 0.01 0.00 0.20 0.09 0.09 P-51 3-19 FH-2A 20.75 0.02 0.00 0.24 0.05 0.05 P-52 FH-1A FH-3A 54.25 0.03 0.00 0.35 0.07 0.07 P-53 FH-3A 3-29 22.50 0.64 0.01 1.02 1.73 1.70 P-54 FH-3A 3-30 0.00 0.00 0.00 0.00 0.00 0.00 2-55 FH-3A 3-31 31.75 0.04 0.00 0.36 0.11 0.11 2-56 J-31 FH-2A 0.25 0.00 0.00 0.00 0.00 0.00 2-57 3-31 FH-4A 3.00 0.00 0.00 0.03 0.00 0.00 2-58 FH-4A 3-32 3.00 0.00 0.00 0.02 0.00 0.00 P-59 FH-4A 3-34 0.00 0.00 0.00 0.00 0.00 0.00 2-6 3-6 3-5 134.46 0.19 0.03 1.53 1.86 1.58 2-60 3-35 FH-102 543.62 0.04 0.01 0.87 0.24 0.18 2-61 J-2 FH-102 706.38 0.40 0.00 1.13 0.29 0.29 _`N P-62 J-35 F-101 1250.00 5.94 0.56 7.98 32.51 29.70 E+�� a��. P-7 3-5 FH-3 68.42 0.02 0.00 0.44 0.12 0.11 2-8 FH-3 J-7 68.42 0.05 0.00 0.44 0.12 0.11 2-9 3-7 FH-1 54.92 0.02 0.00 0.35 0.08 0.07 END NODE RESULTS NODE NODE EXTERNAL HYDRAULIC NODE PRESSURE NODE NAME TITLE DEMAND GRADE ELEVATION HEAD PRESSURE (gpm) (ft) (ft) (ft) (psi) F-101 F-101 1250.00 488.79 345.00 143.79 62.31 410° 1:411 0114011114111 FH-1 0.00 495.63 333.00 162.83 70.56 FH-10 0.00 493.82 308.00 185.82 80.52 FH-102 FH-102 1250.00 495.24 343.00 152.24 65.97 FH-11 0.00 493.62 313.00 180.62 78.27 FH-12 0.00 493.60 313.00 180.60 78.26 FH-13 16.50 494.36 305.00 189.36 82.06 FH-14 0.00 495.92 315.00 180.92 78.40 FH-15 13.50 495.53 306.00 189.53 82.13 FH-16 0.00 495.95 307.00 188.95 81.88 FH-1A 0.00 493.57 316.00 177.57 76.94 FH-2 0.00 495.80 333.00 162.80 70.55 FH-2A 21.00 493.49 316.00 177.49 76.91 FH-3 0.00 495.90 326.00 169.90 73.62 FH-3A 0.00 493.53 320.00 173.53 75.20 FH-4 0.00 495.73 333.00 162.73 70.51 FH-4A 0.00 493.49 318.00 175.49 76.04 FH-5 0.00 495.92 313.00 182.92 79.27 FH-6 0.00 495.91 316.00 179.91 77.96 FH-7 0.00 495.79 309.00 186.79 80.94 FH-8 0.00 495.53 303.00 192.53 83.43 FH-9 0.00 494.62 307.00 187.62 81.30 J-1 0.00 496.07 342.00 154.07 66.76 J-2 0.00 495.65 340.00 155.65 67.45 J-3 6.00 495.72 339.00 156.72 67.91 J-4 10.50 495.81 339.00 156.81 67.95 J-5 16.50 495.92 327.00 168.92 73.20 J-6 0.00 496.14 328.00 168.14 72.86 J-7 7.50 495.85 330.00 165.85 71.87 J-8 6.00 495.83 329.00 166.83 72.29 J-9 21.00 495.81 323.00 172.81 74.88 J-10 10.50 495.86 312.00 183.86 79.67 J-11 0.00 496.71 311.00 185.71 80.47 J-12 0.00 496.46 305.00 191.46 82.96 J-13 0.00 495.97 307.00 188.97 81.89 J-14 12.00 495.92 314.00 181.92 78.83 J-15 15.00 493.36 318.00 175.36 75.99 J-16 4.50 495.91 315.00 180.91 78.40 J-17 10.50 495.81 314.00 181.81 78.78 J-18 13.50 495.71 313.00 182.71 79.18 3-19 15.00 493.51 313.00 180.51 78.22 J-20 7.50 495.53 302.00 193.53 83.86 J-21 18.00 494.87 309.00 185.87 80.55 J-22 12.00 494.76 310.00 184.76 80.06 J-23 0.00 494.42 305.00 189.42 82.08 3-24 4.50 493.50 312.00 181.50 78.65 J-25 6.00 493.80 304.00 189.80 82.25 J-26 18.00 493.32 309.00 184.32 79.87 J-27 0.00 496.45 295.00 201.45 87.29 J-28 36.00 493.01 311.00 182.01 78.87 J-29 22.50 492.87 322.00 170.87 74.05 J-30 0.00 493.53 322.00 171.53 74.33 J-31 28.50 493.49 318.00 175.49 76.04 J-32 3.00 493.49 320.00 173.49 75.18 J-34 0.00 493.49 318.00 175.49 76.04 J-35 J-35 0.00 495.29 343.00 152.29 65.99 R-i Wellborn Ele ---- 497.00 342.00 155.00 67.17 R-2 Flow Test ---- 497.00 311.00 186.00 80.60 SUMMARY OF INFLOWS AND OUTFLOWS (+) INFLOWS INTO THE SYSTEM FROM SUPPLY NODES (-) OUTFLOWS FROM THE SYSTEM INTO SUPPLY NODES NODE FLOWRATE NODE NAME (gpm) TITLE R-1 1820.47 Wellborn Ele R-2 1035.03 Flow Test NET SYSTEM INFLOW = 2855.50 NET SYSTEM OUTFLOW = 0.00 NET SYSTEM DEMAND = 2855.50 ***** HYDRAULIC ANALYSIS COMPLETED ***** P.O.Box 9253,College Station,TX 77842 MEOff/Fax: (979) 690-0329 y , Consulting Enyinee.rs email:civil@rmengineer.corn November 7, 2007 Josh Norton, E.I.T. Graduate Engineer City of College Station 1101 Texas Avenue South College Station,TX 77842 RE: Fire Flow Analysis for A&M Super Storage @ Wellborn—Revision No. 1 4000 Greens Prairie Road West,College Station,TX RME No.213-0304 Josh Norton: There is sufficient capacity in the existing water distribution system to support the above referenced development. This development's water line improvements were integrated into the KYPIPE hydraulic model, generated by this office, for the modeling efforts of the master planned community of Creek Meadows. This hydraulic model is attached and contains pipe distribution modeling within the Wellborn SUD system from Royder Road to Wellborn Oaks and from Greens Prairie Road West to Greens Prairie Trail which will also include the District's elevated storage tank. The existing and proposed improvements, and requirements, for fire flows are summarized below: ❖ The subject property has accessibility to existing public water for both domestic and fire use at the following locations: o Existing 16" PVC public water line located in an existing 16' PUE, along the right-of-way line of Greens Prairie Road West will be relocated (approximately 200 linear feet) into a new 20' PUE required for the dedication of ROW along Greens Prairie Road West. This relocated water line is called P-60 in the KYPIPE hydraulic analysis; o The proposed/relocated 16" PVC public water line will accommodate fire flows to two (2) new fire hydrants set within the property These two hydrants are labeled FH-101 and FH-102 in the KYPIPE model; o Fire hydrant FH-101 will be installed at the end of a new 8" PVC public water line. This new water line is called P-62 in the KYPIPE hydraulic analysis; o Flow tests were obtained from the Wellborn S.UD. from a fire hydrant was installed along the 12" PVC water line that is located on the east side of Greens CD1-213-0304-L09 Page 1 of 3 V 1.' toco3a -o-z-cn q :cs -PC A&M Super Storage @ Wellborn PIEFire Flow Analysis—Revision No.1 Consul-tiny Eny neei^s November 7,2007 Prairie Trail. Since the time of the original flow test the fire hydrant has been removed and an 8" waterline extension has been installed. This flow test was conducted on December 28, 2006 by Wellborn S.U.D. by Mr. Steven Cast and witnessed by this office. The flow data is summarized below in Table #1 —Flow Test Data. TABLE #1 FLOW TEST DATA Flow Pilot Static Fire Static Residual Hydrant Reading Flow Hydrant Pressure Pressure No. Location (psi) (gpm) No. (psi) (psi) FH"A" Greens Prairie Trail 67 1360 Res. 74 70 Note: The reported flow is from the 2.5"nozzle of the identified flow hydrant; ❖ Fire Flow requirements and results: o Commercial fire hydrants will be analyzed to provide a fire flow of 2,500 gpm. This flow may be split between two hydrant so long as they are within 600' of one another; o During fire flow conditions, the proposed system and adjacent infrastructure must provide the required fire flow with a minimum residual pressure of 20 psi; o At all analyzed conditions, no water line shall have a velocity greater than 12 fps in both existing and proposed mains; o Utilizing the KYPIPE model, mentioned above, fire flow requirements for the proposed water system improvements were determined to adequately meet or positively exceed the minimum design standards. Resulting summary information for the fire flow scenario is illustrated below in Table #2 — Water System Summary and identifies the"worse-case" location in the water distribution system (lowest pressure node or highest velocity in pipe). The entire water system model is fully contained with the KYPIPE Hydraulic Analysis Data. TABLE #2 WATER SYSTEM SUMMARY PIPE DATE NODE DATA Residual Fire Flow KYPIPE Pipe Size Flow Velocity Node Pressure Scenerio Name (in) (gpm) (fps) Name (psi) FIRE FLOW CONDITIONS 1 P-62 I 8 1250.00 7.98 I F-101 I 62.31 CD 1-213-0304-L09 Page 2 of 3 A&M Super Storage @Wellborn e........._ MEFire Flow Analysis-Revision No.1 C onsulttn9 Eny net's November 7,2007 Fire Flow Scenario: o 1,250 gpm from FH-101 &FH-102; Please call should you have any questions or require assistance. Sincerely, Agrav.9�,�s e OF•: @`it • . , - 11VAIV.......I •••.•••••••/__..,._... ..., ,,,,. . 90.• ,it 5.3 Q• Rabon A. Metcalf, 13' ,� o. ration@rmengineer.co 4.-. NG��a�•/ • CD1-213-0304-L09 Page 3 of 3 * * * * * * * * * * K Y P I P H 4 * * * * * * * * * * * * * University of Kentucky Network Modeling Software * Copyrighted by KYPIPE LLC * * Version 3 - 11/01/2005 * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * Date & Time: Wed Nov 07 07:14:48 2007 INPUT DATA FILENAME C:\Users\user\RME\Projects\213-03-1\ENGINE-1\0304W1RB.DT2 TABULATED OUTPUT FILENAME C:\Users\user\RME\Projects\213-03-1\ENGINE-1\0304W1RB.OT2 POSTPROCESSOR RESULTS FILENAME C:\Users\user\RME\Projects\213-03-1\ENGINE-1\0304W1RB.RS2 ************************************************ SUMMARY OF ORIGINAL DATA ************************************************ UNITS SPECIFIED FLOWRATE = gallons/minute HEAD (HGL) = feet PRESSURE = psig PIPELINE DATA STATUS CODE: XX -CLOSED PIPE CV -CHECK VALVE P IPE NODE NAMES LENGTH DIAMETER ROUGHNESS MINOR N AME #1 #2 (ft) (in) COEFF. LOSS COEFF. P-1 R-1 J-1 500.00 16.00 139.4518 0.74 P-10 FH-1 J-4 291.00 8.00 139.4518 0.00 P-11 J-7 J-8 162.00 3.00 139.0000 0.00 P-12 J-5 J-9 308.00 6.00 139.0000 6.00 P-13 J-9 FH-2 108.00 6.00 139.4518 0.74 P-14 FH-2 FH-4 812.00 6.00 139.4518 1.31 P-15 FH-4 J-3 291.00 8.00 139.4518 0.00 P-16 J-6 J-11 1670.00 16.00 139.4518 0.00 P-17 J-11 J-12 1320.00 12.00 139.4518 0.74 P-18 J-12 J-13 459.00 8.00 139.4518 1.14 P-19 J-13 FH-7 126.00 8.00 139.4518 6.00 P-2 J-1 J-35 200.00 16.00 139.4518 3.57 P-20 J-13 FH-16 338.00 8.00 139.4518 3.57 P-21 J-14 J-10 146.00 3.00 139.0000 0.00 P-22 J-14 FH-5 68.00 8.00 139.4518 0.40 P-23 FH-5 FH-14 216.00 8.00 139.4518 0.74 P-24 FH-14 J-16 141.00 8.00 139.4518 0.74 P-25 J-16 FH-6 157.00 8.00 139.4518 0.00 P-26 FH-14 J-17 261.00 3.00 139.0000 0.00 P-27 J-16 J-18 304.00 3.00 139.0000 0.00 P-28 FH-7 FH-15 400.00 8.00 139.4518 0.74 P-29 FH-15 FH-8 247.00 6.00 139.4518 0.74 P-3 J-3 J-2 195.00 16.00 139.4518 0.74 P-30 FH-8 J-20 176.00 6.00 139.4518 0.00 P-31 FH-15 J-21 328.00 6.00 139.4518 0.74 P-32 J-21 J-22 219.00 3.00 139.0000 0.00 P-33 J-21 FH-9 205.00 6.00 139.4518 0.00 P-34 FH-9 FH-13 541.00 8.00 139.4518 9.91 P-35 FH-13 J-23 382.00 8.00 139.4518 6.74 P-36 FH-13 FH-10 602.00 8.00 139.4518 9.74 P-37 FH-10 J-25 136.00 3.00 139.0000 0.00 P-38 FH-10 FH-11 341.00 8.00 139.4518 0.74 P-39 FH-11 J-26 267.00 3.00 139.0000 0.00 P-4 J-3 J-4 294.00 16.00 139.4518 0.74 P-40 FH-11 FH-12 443.00 8.00 139.4518 0.00 P-41 FH-12 J-28 145.00 3.00 139.0000 0.00 P-42 3-23 3-1 2842.00 4.00 139.0000 0.00 P-43 3-12 J-27 1933.00 12.00 139.0000 0.00 P-44 J-27 3-23 1640.00 4.00 139.0000 0.00 P-45 J-11 R-2 500.00 16.00 139.4518 0.00 P-46 FH-16 J-14 336.00 8.00 139.4518 0.00 P-47 FH-i1 FH-1A 175.00 8.00 139.0000 0.74 P-48 FH-1A J-15 245.00 3.00 139.0000 0.74 P-49 FH-1A 3-19 322.00 6.00 139.0000 0.74 P-5 J-4 J-6 1207.00 16.00 139.4518 2.24 P-50 J-19 J-24 104.00 3.00 139.0000 0.00 P-51 J-19 FH-2A 399.00 6.00 139.0000 0.17 P-52 FH-1A FH-3A 473.00 8.00 139.0000 0.17 P-53 FH-3A J-29 379.00 3.00 139.0000 0.74 P-54 FH-3A J-30 112.00 8.00 139.0000 0.57 P-55 FH-3A J-31 387.00 6.00 139.0000 0.00 2-56 J-31 FH-2A 197.20 6.00 139.0000 0.74 P-57 J-31 FH-4A 387.87 6.00 139.0000 1.14 P-58 FH-4A J-32 99.00 8.00 139.0000 0.00 P-59 FH-4A J-34 275.00 8.00 139.0000 0.74 266 J-6 102 118.00 6.00 139.4518 0.91 4 age, nw Z� 2-60 1-35 FH-102 200.00 16.00 139.4518 1.14 2-61 FH-102 3-2 1400.00 16.00 139.4518 0.00 P-62 J-35 F-101 200.00 8.00 125.0000 0.57 4.. 1,4144, h w Z % P-7 J-5 FH-3 151.00 8.00 139.4518 0.40 P-8 FH-3 3-7 412.00 8.00 139.4518 0.74 2-9 J-7 FH-1 228.00 8.00 139.4518 0.40 END NODE DATA NODE NODE EXTERNAL JUNCTION EXTERNAL NAME TITLE DEMAND ELEVATION GRADE (gpm) (ft) (ft) F-101 F-101 1250.00 345.00 41,010 FH-1 0.00 333.00 rikartabSQ FH-10 0.00 308.00 FH-102 FH-102 1250.00 343.00 11440.10441.t S FH-11 0.00 313.00 FH-12 0.00 313.00 FH-13 16.50 305.00 FH-14 0.00 315.00 FH-15 13.50 306.00 FH-16 0.00 307.00 FH-1A 0.00 316.00 FH-2 0.00 333.00 FH-2A 21.00 316.00 FH-3 0.00 326.00 FH-3A 0.00 320.00 FH-4 0.00 333.00 FH-4A 0.00 318.00 FH-5 0.00 313.00 FH-6 0.00 316.00 FH-7 0.00 309.00 FH-8 0.00 303.00 FH-9 0.00 307.00 J-1 0.00 342.00 J-2 0.00 340.00 J-3 6.00 339.00 J-4 10.50 339.00 J-5 16.50 327.00 J-6 0.00 328.00 J-7 7.50 330.00 J-8 6.00 329.00 J-9 21.00 323.00 J-10 10.50 312.00 J-11 0.00 311.00 J-12 0.00 305.00 J-13 0.00 307.00 J-14 12.00 314.00 J-15 15.00 318.00 J-16 4.50 315.00 J-17 10.50 314.00 J-18 13.50 313.00 J-19 15.00 313.00 J-20 7.50 302.00 J-21 18.00 309.00 J-22 12.00 310.00 J-23 0.00 305.00 J-24 4.50 312.00 J-25 6.00 304.00 J-26 18.00 309.00 J-27 0.00 295.00 J-28 36.00 311.00 J-29 22.50 322.00 J-30 0.00 322.00 J-31 28.50 318.00 J-32 3.00 320.00 J-34 0.00 318.00 J-35 J-35 0.00 343.00 R-1 Wellborn Ele ---- 342.00 497.00 R-2 Flow Test ---- 311.00 497.00 OUTPUT OPTION DATA OUTPUT SELECTION: ALL RESULTS ARE INCLUDED IN THE TABULATED OUTPUT SYSTEM CONFIGURATION NUMBER OF PIPES (p) = 62 NUMBER OF END NODES (j) = 56 NUMBER OF PRIMARY LOOPS (1) = 5 NUMBER OF SUPPLY NODES (f) = 2 NUMBER OF SUPPLY ZONES (z) = 1 Case: 0 RESULTS OBTAINED AFTER 8 TRIALS: ACCURACY = 0.00000 SIMULATION DESCRIPTION (LABEL) M.D.W. Centre - Phase One PIPELINE RESULTS STATUS CODE: XX -CLOSED PIPE CV -CHECK VALVE PIPE NODE NUMBERS FLOWRATE HEAD MINOR LINE HL+ML/ HL/ NAME #1 #2 LOSS LOSS VELO. 1000 1000 (gpm) (ft) (ft) (ft/s) (ft/ft) (ft/ft) P-i R-1 3-1 1820.47 0.83 0.10 2.90 1.86 1.66 P-10 FH-1 J-4 54.92 0.02 0.00 0.35 0.07 0.07 P-11 J-7 J-8 6.00 0.02 0.00 0.27 0.15 0.15 2-12 3-5 J-9 49.54 0.08 0.03 0.56 0.35 0.25 2-13 J-9 FH-2 28.54 0.01 0.00 0.32 0.10 0.09 2-14 FH-2 FH-4 28.54 0.07 0.00 0.32 0.09 0.09 2-15 811-4 3-3 28.54 0.01 0.00 0.18 0.02 0.02 P-16 3-11 J-6 773.88 0.57 0.00 1.23 0.34 0.34 2-17 3-11 J-12 261.15 0.24 0.01 0.74 0.19 0.19 2-18 3-12 3-13 220.81 0.45 0.04 1.41 1.05 0.98 P-19 3-13 FH-7 169.81 0.08 0.11 1.08 1.47 0.60 P-2 3-1 3-35 1793.62 0.32 0.45 2.86 3.89 1.62 P-20 J-13 FH-16 51.00 0.02 0.01 0.33 0.08 0.06 2-21 J-14 3-10 10.50 0.06 0.00 0.48 0.41 0.41 2-22 J-14 FH-5 28.50 0.00 0.00 0.18 0.03 0.02 2-23 FH-5 FH-14 28.50 0.00 0.00 0.18 0.02 0.02 2-24 FH-14 3-16 18.00 0.00 0.00 0.11 0.01 0.01 2-25 J-16 FH-6 0.00 0.00 0.00 0.00 0.00 0.00 2-26 FH-14 3-17 10.50 0.11 0.00 0.48 0.41 0.41 2-27 3-16 3-18 13.50 0.20 0.00 0.61 0.66 0.66 2-28 FH-7 FH-15 169.81 0.24 0.01 1.08 0.64 0.60 P-29 FH-15 FH-8 7.50 0.00 0.00 0.09 0.01 0.01 2-3 3-3 J-2 706.38 0.06 0.01 1.13 0.36 0.29 2-30 FH-8 J-20 7.50 0.00 0.00 0.09 0.01 0.01 2-31 FH-15 3-21 148.81 0.63 0.03 1.69 2.01 1.91 P-32 3-21 J-22 12.00 0.12 0.00 0.54 0.53 0.53 2-33 3-21 FH-9 118.81 0.26 0.00 1.35 1.26 1.26 2-34 FH-9 FH-13 118.81 0.17 0.09 0.76 0.47 0.31 2-35 3-23 FH-13 67.19 0.04 0.02 0.43 0.16 0.11 2-36 FH-13 FH-10 169.50 0.36 0.18 1.08 0.89 0.60 2-37 811-10 J-25 6.00 0.02 0.00 0.27 0.15 0.15 2-38 FH-10 FH-11 163.50 0.19 0.01 1.04 0.60 0.56 2-39 FH-11 J-26 18.00 0.30 0.00 0.82 1.12 1.12 2-4 3-4 3-3 683.84 0.08 0.01 1.09 0.32 0.27 2-40 FH-11 FH-12 36.00 0.02 0.00 0.23 0.03 0.03 2-41 FH-12 J-28 36.00 0.59 0.00 1.63 4.06 4.06 2-42 3-1 J-23 26.85 1.65 0.00 0.69 0.58 0.58 2-43 3-12 J-27 40.34 0.01 0.00 0.11 0.01 0.01 2-44 3-27 J-23 40.34 2.03 0.00 1.03 1.24 1.24 2-45 R-2 3-11 1035.03 0.29 0.00 1.65 0.58 0.58 2-46 FH-16 3-14 51.00 0.02 0.00 0.33 0.06 0.06 P-47 FH-11 FH-1A 109.50 0.05 0.01 0.70 0.30 0.27 2-48 FH-1A 3-15 15.00 0.20 0.01 0.68 0.82 0.80 2-49 FH-1A 3-19 40.25 0.05 0.00 0.46 0.18 0.17 P-5 3-6 3-4 639.42 0.29 0.04 1.02 0.27 0.24 P-50 3-19 3-24 4.50 0.01 0.00 0.20 0.09 0.09 2-51 3-19 FH-2A 20.75 0.02 0.00 0.24 0.05 0.05 P-52 FH-1A FH-3A 54.25 0.03 0.00 0.35 0.07 0.07 P-53 FH-3A 3-29 22.50 0.64 0.01 1.02 1.73 1.70 2-54 FH-3A 3-30 0.00 0.00 0.00 0.00 0.00 0.00 P-55 FH-3A 3-31 31.75 0.04 0.00 0.36 0.11 0.11 2-56 3-31 FH-2A 0.25 0.00 0.00 0.00 0.00 0.00 P-57 3-31 FH-4A 3.00 0.00 0.00 0.03 0.00 0.00 2-58 FH-4A 3-32 3.00 0.00 0.00 0.02 0.00 0.00 2-59 FH-4A 3-34 0.00 0.00 0.00 0.00 0.00 0.00 P-6 3-6 3-5 134.46 0.19 0.03 1.53 1.86 1.58 2-60 3-35 FH-102 543.62 0.04 0.01 0.87 0.24 0.18 1141146, ��` P-61 3-2 FH-102 706.38 0.40 0.00 1.13 0.29 0.29 N 2-62 3-35 F-101 1250.00 5.94 0.56 7.98 32.51 29.70 F P-7 3-5 FH-3 68.42 0.02 0.00 0.44 0.12 0.11 2-8 FH-3 3-7 68.42 0.05 0.00 0.44 0.12 0.11 2-9 3-7 FH-1 54.92 0.02 0.00 0.35 0.08 0.07 END NODE RESULTS NODE NODE EXTERNAL HYDRAULIC NODE PRESSURE NODE NAME TITLE DEMAND GRADE ELEVATION HEAD PRESSURE (gpm) (ft) (ft) (ft) (psi) F-101 F-101 1250.00 488.79 345.00 143.79 62.31 4106 Nig 041110,11 FH-1 0.00 495.83 333.00 162.83 70.56 811-10 0.00 493.82 308.00 185.82 80.52 FH-102 FH-102 1250.00 495.24 343.00 152.24 65.97 FH-11 0.00 493.62 313.00 180.62 78.27 FH-12 0.00 493.60 313.00 180.60 78.26 FH-13 16.50 494.36 305.00 189.36 82.06 FH-14 0.00 495.92 315.00 180.92 78.40 FH-15 13.50 495.53 306.00 189.53 82.13 FH-16 0.00 495.95 307.00 188.95 81.88 FH-1A 0.00 493.57 316.00 177.57 76.94 FH-2 0.00 495.80 333.00 162.80 70.55 FH-2A 21.00 493.49 316.00 177.49 76.91 FH-3 0.00 495.90 326.00 169.90 73.62 FH-3A 0.00 493.53 320.00 173.53 75.20 FH-4 0.00 495.73 333.00 162.73 70.51 FH-4A 0.00 493.49 318.00 175.49 76.04 FH-5 0.00 495.92 313.00 182.92 79.27 FH-6 0.00 495.91 316.00 179.91 77.96 FH-7 0.00 495.79 309.00 186.79 80.94 FH-8 0.00 495.53 303.00 192.53 83.43 FH-9 0.00 494.62 307.00 187.62 81.30 J-1 0.00 496.07 342.00 154.07 66.76 J-2 0.00 495.65 340.00 155.65 67.45 J-3 6.00 495.72 339.00 156.72 67.91 J-4 10.50 495.81 339.00 156.81 67.95 J-5 16.50 495.92 327.00 168.92 73.20 J-6 0.00 496.14 328.00 168.14 72.86 J-7 7.50 495.85 330.00 165.85 71.87 J-8 6.00 495.83 329.00 166.83 72.29 J-9 21.00 495.81 323.00 172.81 74.88 J-10 10.50 495.86 312.00 183.86 79.67 J-11 0.00 496.71 311.00 185.71 80.47 J-12 0.00 496.46 305.00 191.46 82.96 J-13 0.00 495.97 307.00 188.97 81.89 J-14 12.00 495.92 314.00 181.92 78.83 J-15 15.00 493.36 318.00 175.36 75.99 J-16 4.50 495.91 315.00 180.91 78.40 7-17 10.50 495.81 314.00 181.81 78.78 1-18 13.50 495.71 313.00 182.71 79.18 J-19 15.00 493.51 313.00 180.51 78.22 J-20 7.50 495.53 302.00 193.53 83.86 J-21 18.00 494.87 309.00 185.87 80.55 J-22 12.00 494.76 310.00 184.76 80.06 J-23 0.00 494.42 305.00 189.42 82.08 J-24 4.50 493.50 312.00 181.50 78.65 J-25 6.00 493.80 304.00 189.80 82.25 J-26 18.00 493.32 309.00 184.32 79.87 J-27 0.00 496.45 295.00 201.45 87.29 J-28 36.00 493.01 311.00 182.01 78.87 J-29 22.50 492.87 322.00 170.87 74.05 J-30 0.00 493.53 322.00 171.53 74.33 J-31 28.50 493.49 318.00 175.49 76.04 J-32 3.00 493.49 320.00 173.49 75.18 J-34 0.00 493.49 318.00 175.49 76.04 J-35 J-35 0.00 495.29 343.00 152.29 65.99 R-1 Wellborn Ele ---- 497.00 342.00 155.00 67.17 R-2 Flow Test ---- 497.00 311.00 186.00 80.60 SUMMARY OF INFLOWS AND OUTFLOWS (+) INFLOWS INTO THE SYSTEM FROM SUPPLY NODES (-) OUTFLOWS FROM THE SYSTEM INTO SUPPLY NODES NODE FLOWRATE NODE NAME (gpm) TITLE R-1 1820.47 Wellborn Ele R-2 1035.03 Flow Test NET SYSTEM INFLOW = 2855.50 NET SYSTEM OUTFLOW = 0.00 NET SYSTEM DEMAND = 2855.50 ***** HYDRAULIC ANALYSIS COMPLETED ***** Rabon A. Metcalf, P.E. From: Stephen Cast[wsud.scc@verizon.net] Sent: Tuesday, November 06, 2007 3:39 PM To: Rabon A. Metcalf, P.E. Subject: Re: FW: Rabon, The 16" line relocation on the Hub Kennedy tract is approved with the proposed 45 degree fittings and using the existing 16"gate valves to control water flow. Stephen Cast Wellborn SUD Original Message From: "Rabon A.Metcalf,P.E."<rabon@rmengineer.com> To: "'Stephen Cast"'<wsud.scc@verizon.net> Sent:Tuesday,October 23,2007 7:27 AM Subject Rabon A.Metcalf,P.E. RME Consulting Engineers 1391 Seamist Lane<77845> P.O.Box 9253 College Station,TX 77842 PH: (979)690-0329 FX: (979)690-0329 MB: (979)219-4174 THE ELECTRONIC DATA,CONTENT,INFORMATION,AND/OR DRAWINGS GENERATED,BY RME CONSULTING ENGINEERS(RME),ATTACHED OR CONTAINED IN THIS ELECTRONIC TRANSMITTAL IS CONSIDERED BY RME TO BE CONFIDENTIAL. WHEN ISSUED,IT'S USE IS INTEND SOLELY FOR THE INDIVIDUAL OR ENTITY TO WHICH IT IS ADDRESSED. THIS MATERIAL IS INTENDED FOR USE BY THE RECIPIENT NAMED,ONLY,AND PERMISSION IS NOT GRANTED TO THE RECIPIENT FOR DISTRIBUTION OF THESE DOCUMENTS IN ANY FORM OR FASHION. THE RECIPIENT UNDERSTANDS THAT THIS DATA IS AUTHORIZED"AS IS"WITHOUT ANY WARRANTY AS TO ITS PERFORMANCE, ACCURACY,FREEDOM FROM ERROR,OR AS TO ANY RESULTS GENERATED THROUGH ITS USE. THE RECIPIENT ALSO UNDERSTANDS AND AGREES THAT RME,UPON RELEASE OF SUCH DATA,IS NO LONGER RESPONSIBLE FOR THEIR USE OR MODIFICATION. THE USER AND RECIPIENT OF THE ELECTRONIC DATA ACCEPTS FULL RESPONSIBILITY AND LIABILITY FOR ANY CONSEQUENCES ARISING OUT OF THEIR USE. Original Message From:tcarnes@sidebyte.com[mailto:tcarnes@sidebyte.com] Sent: Saturday,October 20,2007 10:20 AM To:Bexco Operating;Rabon A.Metcalf,P.E. Subject:Re:FW: I agree why spend money to help a tract of land we may or may not ever own. I say no we have to pass. Sent via BlackBerry by AT&T Original Message -1cxJc From: Pat Baker<bexcol @hues.net> n �j( Date: Sat,20 Oct 2007 09:52:06 (k To:"Rabon A.Metcalf,P.E."<rabon@rmengineer.com>Cc:"'Todd Carnes"' <tcarnes@sidebyte.com> Subject:Re:FW: 1 AC P.O.Box 9253,College Station,TX 77842 11EOff/Fax: (979) 690-0329 Gonsu/ting Engineer's email:civil@rmengineer.com 7 2008 r� c� February , /1 , Josh Norton, E.I.T. Cy� Graduate Engineer City of College Station 1101 Texas Avenue South \� College Station, TX 77842 RE: Fire Flow Report for A&M Super Storage @ Wellborn 4000 Greens Prairie Road West,College Station,TX RME No.213-0304 Josh Norton: A fire flow test was performed in accordance with National Fire Prevention Association (NFPA) Standard 291, Chapter 4, for the above referenced project, on February 5, 2008. The results of this test are shown on the attached data sheet, and are sufficient to meet the City of College Station minimum design standards for fire flow requirements. Please call should you have any questions. Sincerely, V • • A. METCALF 4.... Rabon A. Metcalf, P. 4583 rabon@rinengineer.co p ' �C T••�� At S/ONA ENG'ii 041#14A r if Adam J. B Baugh, E.I.T, adam@rmengineer.com CD1-213-0304-L15 Page 1 of 1 FIRE FLOW TEST REPORT Date February 5, 2008 Nozzle size 2.5 Location A&M Super Storage at Wellborn Flow Hydrant Desc. FN. @ Sown/CAST' CoPNF2 of A -iri 5c Pti 7?iR6G 6 Lord ( &< 1.. Pitot Reading 5 5 GPM 124o Static Hydrant Desc. vcrrN mos'r Fige ty i)gotvT chi iL.Ve52 .5PRbu ,S C Static PSI 42 Residual PSI (DZ COMMENTS: if �. ;I%r/ 2 ' �'� ` i ,� ate Signature, i+ aikkv • : f, i Z/Sei0O8 ate Signat e, Title / 400' RME Consulting Engineers POST OFFICE BOX 9253 MECOLLEGE STATION,TEXAS 77842 OFF/FAX: (979)690-0329 Gonsu/ttn Engineers m ,, 9E-mail: civil@rmengineer.co P.O.Box 9253,College Station,TX 77842 Clir Off/Fax: (979)690-0329 e Eriyireer3 email:civil@rmengineer.com October 29,2007 Josh Norton,E.I.T. Graduate Engineer City of College Station 1101 Texas Avenue South College Station,TX 77842 RE: Fire Flow Analysis for A&M Super Storage @ Wellborn 4000 Greens Prairie Road West,College Station,TX RME No,213-0304 Josh Norton: There is sufficient capacity in the existing water distribution system to support the above referenced development. This development's water line improvements were integrated into the KYPIPE hydraulic model, generated by this office, for the modeling efforts of the master planned community of Creek Meadows. This hydraulic model is attached and contains pipe distribution modeling within the Wellborn SUD system from Royder Road to Wellborn Oaks and from Greens Prairie Road West to Greens Prairie Trail which will also include the District's elevated storage tank. The existing and proposed improvements, and requirements, for fire flows are summarized below: + The subject property has accessibility to existing public water for both domestic and fire use at the following locations: o Existing 16" PVC public water line located in an existing 16' PUE, along the right-of-way line of Greens Prairie Road West will be relocated (approximately 200 linear feet) into a new 20' PUE required for the dedication of ROW along Greens Prairie Road West. This water line is called P-60 in the KYPIPE hydraulic analysis; o The proposed/relocated 16" PVC public water line will accommodate fire flows to two (2) new fire hydrants set within the property These two hydrants are labeled FH-101 and FH-l02 in the KYPIPE model; o Flow tests were obtained from the Wellborn S.UD. from a fire hydrant was installed along the 12" PVC water line that is located on the east side of Greens Prairie Trail. Since the time of the original flow test the fire hydrant has been removed and an 8" waterline extension has been installed. This flow test was conducted on December 28, 2006 by Wellborn S.U.D. by Mr. Steven Cast and witnessed by this office. The flow data is summarized below in Table#1 —Flow Test Data. CDI-213-0304-L07 Page 1 of 2 A&M Super Storage @ Wellborn MEFire Flow Analysis Cored-tiny i g October 29,2007 TABLE#1 FLOW TEST DATA Flow Pilot Static Fire Static Residual Hydrant Reading Flow Hydrant Pressure Pressure No. Location (psi) (gpm) No. (Psi) (Psi) FH"A" Greens Prairie Trail 67 1360 Res. 74 70 Note: The reported flow is from the 2.5"nozzle of the identified flow hydrant; + Fire Flow requirements and results: o Commercial fire hydrants will be analyzed to provide a fire flow of 2,500 gpm. This flow may be split between two hydrant so long as they are within 600' of one another; o During fire flow conditions,the proposed system and adjacent infrastructure must provide the required fire flow with a minimum residual pressure of 20 psi; o At all analyzed conditions,no water line shall have a velocity greater than 12 fps in both existing and proposed mains; o Utilizing the KYPIPE model, mentioned above, fire flow requirements for the proposed water system improvements were determined to adequately meet or positively exceed the minimum design standards. Resulting summary information for the fire flow scenario is illustrated below in Table #2 — Water System Summary and identifies the"worse-case"location in the water distribution system (lowest pressure node or highest velocity in pipe). The entire water system model is fully contained with the KYPIPE Hydraulic Analysis Data. TABLE#2 WATER SYSTEM SUMMARY PIPE DATE NODE DATA Residual Fire Flow KYPIPE Pipe Size Flow Velocity Node Pressure Scenerio Name (in) (gpm) (fps) Name (psi) FIRE FLOW CONDITIONS 1 I P-1 I 16 1820.47 2.90 ) FH-1.02 I 65.97 Fire Flow Scenario: o 1,250 gpm from FH-101 &FH-102; Please call should you have any questions or require as 'stance. Sincerely, ..ci► , .FT ,4\ 111. 11011r Rabon A.Metcalf,P.E. .„„#I I-- • rabon@tmengineer.com � c+ RABON A. METCALF CD 1-213-0304-L07 1)�' 88583 O 7-11 ( � " Page 2 of 2 kk oNAL 04,E * * * * * * * * * * K Y P I P E 4 * * * * * * * * * * * * * University of Kentucky Network Modeling Software * * * * Copyrighted by KYPIPE LLC * * Version 3 - 11/01/2005 * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * Date & Time: Tue Oct 30 18:06:12 2007 INPUT DATA FILENAME C:\Users\user\RME\Projects\213-03-1\ENGINE-1\0304W1RA.DT2 TABULATED OUTPUT FILENAME C:\Users\user\RME\Projects\213-03-1\ENGINE-1\0304W1RA.OT2 POSTPROCESSOR RESULTS FILENAME C:\Users\user\RME\Projects\213-03-1\ENGINE-1\0304W1RA.RS2 SUMMARY OF O R I G I NAL DATA UNITS SPECIFIED FLOWRATE = gallons/minute HEAD (HGL) = feet PRESSURE = psig PIPELINE DATA STATUS CODE: XX -CLOSED PIPE CV -CHECK VALVE P IPE NODE NAMES LENGTH DIAMETER ROUGHNESS MINOR N AME #1 #2 (ft) (in) COEFF. LOSS COEFF. P-1 R-1 J-1 500.00 16.00 139.4518 0.74 9-10 FH-1 J-4 291.00 8.00 139.4518 0.00 P-11 J-7 3-B 162.00 3.00 139.0000 0.00 9-12 J-5 J-9 308.00 6.00 139.0000 6.00 9-13 J-9 FH-2 108.00 6.00 139.4518 0.74 9-14 FH-2 FH-4 812.00 6.00 139.4518 1.31 9-15 FH-4 J-3 291.00 8.00 139.4518 0.00 9-16 J-6 J-11 1670.00 16.00 139.4518 0.00 9-17 J-11 J-12 1320.00 12.00 139.4518 0.74 9-18 J-12 J-13 459.00 8.00 139.4518 1.14 9-19 J-13 FH-7 126.00 8.00 139.4518 6.00 9-2 J-1 FH-101 200.00 16.00 139.4518 3.57 9-20 J-13 FH-16 338.00 8.00 139.4518 3.57 9-21 J-14 J-10 146.00 3.00 139.0000 0.00 9-22 J-14 FH-5 68.00 8.00 139.4518 0.40 9-23 FH-5 FH-14 216.00 8.00 139.4518 0.74 9-24 FH-14 J-16 141.00 8.00 139.4518 0.74 9-25 J-16 FH-6 157.00 8.00 139.4518 0.00 9-26 FH-14 J-17 261.00 3.00 139.0000 0.00 9-27 J-16 J-18 304.00 3.00 139.0000 0.00 9-28 FH-7 FH-15 400.00 8.00 139.4518 0.74 9-29 FH-15 FH-8 247.00 6.00 139.4518 0.74 9-3 J-3 J-2 195.00 16.00 139.4518 0.74 9-30 FH-8 J-20 176.00 6.00 139.4518 0.00 9-31 FH-15 J-21 328.00 6.00 139.4518 0.74 9-32 J-21 J-22 219.00 3.00 139.0000 0.00 9-33 J-21 FH-9 205.00 6.00 139.4518 0.00 9-34 911-9 FH-13 541.00 8.00 139.4518 9.91 9-35 FH-13 J-23 382.00 8.00 139.4518 6.74 9-36 FH-13 F11-10 602.00 8.00 139.4518 9.74 9-37 FH-10 J-25 136.00 3.00 139.0000 0.00 P-38 FH-10 FH-11 341.00 8.00 139.4518 0.74 9-39 FH-11 J-26 267.00 3.00 139.0000 0.00 9-4 3-3 3-4 294.00 16.00 139.4518 0.74 9-40 FH-11 FH-12 443.00 8.00 139.4518 0.00 9-41 FH-12 3-28 145.00 3.00 139.0000 0.00 9-42 3-23 3-1 2842.00 4.00 139.0000 0.00 9-43 1-12 3-27 1933.00 12.00 139.0000 0.00 9-44 3-27 3-23 1640.00 4.00 139.0000 0.00 9-45 3-11 R-2 500.00 16.00 139.4518 0.00 9-46 FR-16 3-14 336.00 8.00 139.4518 0.00 9-47 FH-11 FH-1A 175.00 8.00 139.0000 0.74 9-48 FR-1A 3-15 245.00 3.00 139.0000 0.74 9-49 FR-1A 3-19 322.00 6.00 139.0000 0.74 P-5 3-4 3-6 12.07.00 16.00 139.4518 2.24 9-50 3-19 3-24 104.00 3.00 139.0000 0.00 9-51 3-19 FH-2A 399.00 6.00 139.0000 0.17 9-52 FR-1A FR-3A 473.00 8.00 139.0000 0.17 9-53 FH-3A 3-29 379.00 3.00 139.0000 0.74 P-54 FH-3A 3-30 112.00 8.00 139.0000 0.57 9-55 FH-3A 3-31 387.00 6.00 139.0000 0.00 9-56 J-31 FH-2A 197.20 6.00 139.0000 0.74 9-57 3-31 FH-4A 387.87 6.00 139.0000 1.14 9-58 FH-4A 3-32 99.00 8.00 139.0000 0.00 9-59 FH-4A 3-34 275.00 8.00 139.0000 0.74 960 3-6 102 118.00 6.00 139.4518 0.91 A. & 9-60 FH-101 FH-102 200.00 16.00 139.4518 11.14 P-61 FH-102 3-2 1400.00 16.00 139.4518 0.00 P-7 J-5 FH-3 151.00 8.00 139.4518 0.40 ID i C►Ci 9-8 FH-3 3-7 412.00 8.00 139.4518 0.74 %A P-9 J-7 FR-1 228.00 8.00 139.4518 0.40 L'_!Co h END 4414111 NODE DATA NODE NODE EXTERNAL JUNCTION EXTERNAL NAME TITLE DEMAND ELEVATION GRADE (gPM) (ft) (ft) FH-1 0.00 333.00 F- 00 0.00 343.00 I 2 * �ae FH-101 FH-101 1250.00 34.3.00 �j FH-102 FH-102 1250.00 343.00ftwommo _IL FH-11 0..00 313.00 FitAtANS1 FH-12 0.00 313.00 7 FH-13 16.50 305.00 FH-14 0.00 315.00 FH-15 13.50 306.00 FH-16 0.00 307.00 FH-1A 0.00 316.00 FH-2 0.00 333.00 FH-2A 21.00 316.00 FH-3 0.00 326.00 FH-3A 0.00 320.00 FR-4 0.00 333.00 FH-4A 0.00 318.00 FH-5 0.00 313.00 FH-6 0.00 316.00 FH-7 0.00 309.00 EH-8 0.00 303.00 FH-9 0.00 307.00 J-1 0.00 342.00 J-2 0.00 340.00 J-3 6.00 339.00 J-4 10.50 339.00 J-5 16.50 327.00 J-6 0.00 328.00 J-7 7.50 330.00 3-8 6.00 329.00 J-9 21.00 323.00 J-10 10.50 312.00 J-11 0.00 311.00 J-12 0.00 305.00 J-13 0.00 307.00 J-14 12.00 314.00 J-15 15.00 318.00 J-16 4.50 315.00 J-17 10.50 314.00 J-18 13.50 313.00 J-19 15.00 313.00 J-20 7.50 302.00 J-21 18.00 309.00 J-22 12.00 310.00 J-23 0.00 305.00 J-24 4.50 312.00 J-25 6.00 304.00 J-26 18.00 309.00 J-27 0.00 295.00 J-28 36.00 311.00 J-29 22.50 322.00 J-30 0.00 322.00 J-31 28.50 318.00 J-32 3.00 320.00 J-34 0.00 318.00 R-1 Wellborn Ele ---- 342.00 497.00 R-2 Flow Test ---- 311.00 497.00 O UTPUT OPTION DATA OUTPUT SELECTION: ALL RESULTS ARE INCLUDED IN THE TABULATED OUTPUT S YSTEM CONFIGURATION NUMBER OF PIPES (p) = 61 NUMBER OF END NODES (j) = 55 NUMBER OF PRIMARY LOOPS (1) = 5 NUMBER OF SUPPLY NODES (f) = 2 NUMBER OF SUPPLY ZONES (z) = 1 Case: 0 RESULTS OBTAINED AFTER 8 TRIALS: ACCURACY = 0.00000 S IMULATION DESCRIPTION (L A B E L) M.D.W. Centre - Phase One P IPELINE RESULTS STATUS CODE: XX -CLOSED PIPE CV -CHECK VALVE P IPE NODE NUMBERS FLOWRATE HEAD MINOR LINE HL+ML/ HL/ N AME #1 #2 LOSS LOSS VELO. 1000 1000 (gpm) (ft) (ft) (ft/s) (ft/ft) (ft/ft) P-1 R-1 J-1 1820.47 0.83 0.10 2.90 1.86 1.661 (IS4 s P-10 FH-1 3-4 54.92 0.02 0.00 0.35 0.07 0.07 P-11 J-7 J-8 6.00 0.02 0.00 0.27 0.15 0.15 O@$ 11Z P-13 P-12 J-5 J-9 49.54 0.08 0.03 0.56 0.35 0.25 ��'' '' {{ P-13 J-9 FH-2 28.54 0.01 0.00 0.32 0.10 0.09 10402.4 2-14 FH-2 FH-4 28.54 0.07 0.00 0.32 0.09 0.09 2-15 FH-4 3-3 28.54 0.01 0.00 0.18 0.02 0.02 2-16 3-11 3-6 773.88 0.57 0.00 1.23 0.34 0.34 2-17 3-11 3-12 261.15 0.24 0.01 0.74 0.19 0.19 2-18 3-12 3-13 220.81 0.45 0.04 1.41 1.05 0.98 2-19 3-13 F1{-7 169.81 0.08 0.11 1.08 1.47 0.60 2-2 J-1 FH-101 1793.62 0.32 0.45 2.86 3.89 1.62 2-20 3-13 FH-16 51.00 0.02 0.01 0.33 0.08 0.06 2-21 3-14 3-10 10.50 0.06 0.00 0.48 0.41 0.41 2-22 3-14 FH-5 28.50 0.00 0.00 0.18 0.03 0.02 2-23 FH-5 FH-14 28.50 0.00 0.00 0.18 0.02 0.02 2-24 FH-14 3-16 18.00 0.00 0.00 0.11 0.01 0.01 2-25 3-16 FH-6 0.00 0.00 0.00 0.00 0.00 0.00 2-26 FH-14 3-17 10.50 0.11 0.00 0.48 0.41 0.41 2-27 3-16 3-18 13.50 0.20 0.00 0.61 0.66 0.66 2-28 FH-7 F14-15 169.81 0.24 0.01 1.08 0.64 0.60 2-29 FH-15 FH-8 7.50 0.00 0.00 0.09 0.01 0.01 2-3 3-3 3-2 706.38 0.06 0.01 1.13 0.36 0.29 2-30 FH-8 J-20 7.50 0.00 0.00 0.09 0.01 0.01 P-31 FH-15 3-21 148.81 0.63 0.03 1.69 2.01 1.91 2-32 3-21 3-22 12.00 0.12 0.00 0.54 C.53 0.53 2-33 3-21 FH-9 118.81 0.26 0.00 1.35 1.26 1.26 2-34 FH-9 211-13 118.81 0.17 0.09 0.76 0.47 0.31 2-35 3-23 211-13 67.19 0.04 0.02 0.43 0.16 0.11 2-36 211-13 FH-10 169.50 0.36 0.18 1.08 0.89 0.60 2-37 FR-10 3-25 6.00 0.02 0.00 0.27 0.15 0.15 2-38 FR-10 FR-11 163.50 0.19 0.01 1.04 0.60 0.56 P-39 FH-11 3-26 18.00 0.30 0.00 0.82 1.12 1.12 2-4 3-4 J-3 683,84 0.08 0.01 1.09 0.32 0.27 2-40 FH-1.1 211-12 36.00 0.02 0.00 0.23 0.03 0.03 2-41 211-12 3-28 36.00 0.59 0.00 1.63 4.06 4.06 P-42 3-1 3-23 26.85 1.65 0.00 0.69 0.58 0.58 2-43 3-12 3-27 40.34 0.01 0.00 0.11 0.01 0.01 p-44 3-27 3-23 40.34 2.03 0.00 1.03 1.24 1.24 P-45 11-2 3-1.1 1035.03 0.29 0.00 1.65 0.58 C.58 2-46 211-16 3-14 51.00 0.02 0.00 0.33 0.06 0.06 P-47 FR-11 FH-1A 109.50 0.05 0.01 0.70 0.30 0.27 2-48 FH-1A 3-15 15.00 0.20 0.01 0.68 0.82 0.80 2-49 FH-1A 3-19 40.25 0.05 0.00 0.46 0.18 0.17 2-5 3-6 3-4 639.42 0.29 0.04 1.02 0.27 0.24 2-50 3-19 3-24 4.50 0.01 0.00 0.20 0.09 C.09 2-51 3-19 FH-2A 20.75 0.02 0.00 0.24 0.05 0.05 P-52 FH-1A FH-3A 54.25 0.03 0.00 0.35 0.07 0.07 P-53 FH-3A 3-29 22.50 0.64 0.01 1.02 1.73 1.70 2-54 FH-3A 3-30 0.00 0.00 0.00 0.00 0.00 0.00 P-55 F11-3A 3-31 31.75 0.04 0.00 0.36 0.11 0.11 2-56 3-31 FH-2A 0.25 0.00 0.00 0.00 0.00 0.00 2-57 3-31 FH-4A 3.00 0.00 0.00 0.03 0.00 0.00 2-58 FH-4A 3-32 3.00 0.00 0.00 0.02 0.00 0.00 2-59 FH-4A 3-34 0.00 0.00 0.00 0.00 0.00 0.00 2-6 3-6 3-5 134.46 0.19 0.03 1.53 1.86 1.58 2-60 211-101 211-102 543.62 0.04 0.01 0.87 0.24 0.18 2-61 3-2 FR-102 706.38 0.40 0.00 1.13 0.29 0.29 2-7 3-5 FH-3 68.42 0.02 0.00 0.44 0.12 0.11 2-8 211-3 3-7 68.42 0.05 0.00 0.44 0.12 0.11 2-9 3-7 FH-1 54.92 0.02 0.00 0.35 0.08 0.07 END NODE RESULTS NODE NODE EXTERNAL HYDRAULIC NODE PRESSURE NODE NAME TITLE DEMAND GRADE ELEVATION HEAD PRESSURE (qpm) (ft) (ft) (ft) (psi) 211-1 0.00 495.83 333.00 162.83 70.56 FH-10 0.00 493.82 308.00 185.82 80.52 FH-101 FH-101 1250.00 495.29 343.00 152.29 65.99 06142011014 �,_ _w_�r, 28-102 211-102 1250.00 495.24 343.00 152.24 65.97 I� N FR-11 0.00 493.62 313.00 180.62 78.27 211-12 0.00 493.60 313.00 180.60 78.26 611e FH-13 16.50 494.36 305.00 189.36 82.06 FH-14 0.00 495.92 315.00 19.92 78.40 FH-15 13.50 495.53 306.00 18 .53 82.13 FH-16 0.00 495.95 307.00 188.95 81.88 FH-1A 0.00 493.57 316.00 177.57 76.94 FH-2 0.00 495.80 333.00 162.80 70.55 FH-2A 21.00 493.49 316.00 177.49 76.91 FH-3 0.00 495.90 326.00 169.90 73.62 FH-3A 0.00 493.53 320.00 173.53 75.20 FH-4 0.00 495.73 333.00 162.73 70.51 FH-4A 0.00 493.49 318.00 175.49 76.04 FH-5 0.00 495.92 313.00 182.92 79.27 FH-6 0.00 495.91 316.00 179.91 77.96 FH-7 0.00 495.79 309.00 186.79 80.94 FH-8 0.00 495.53 303.00 192.53 83.43 FH-9 0.00 494.62 307.00 187.62 81.30 3-1 0.00 496.07 342.00 154.07 66.76 J-2 0.00 495.65 340.00 155.65 67.45 3-3 6.00 495.72 339.00 156.72 67.91 J-4 10.50 495.81 339.00 156.81 67.95 3-5 16.50 495.92 327.00 168.92 73.20 3-6 0.00 496.14 328.00 168.14 72.86 J-7 7.50 495.85 330.00 165.85 71.87 J-8 6.00 495.83 329.00 166.83 72.29 J-9 21.00 495.81 323.00 172.81 74.88 3-10 10.50 495.86 312.00 183.86 79.67 3-11 0.00 496.71 311.00 185.71 80.47 3-12 0.00 496.46 305.00 191.46 82.96 3-13 0.00 495.97 307.00 188.97 81.89 3-14 12.00 495.92 314.00 181.92 78.83 3-15 15.00 493.36 318.00 175.36 75.99 3-16 4.50 495.91 315.00 180.91 78.40 3-17 10.50 495.81 314.00 181.81 78.78 3-18 13.50 495.71 313.00 182.71 79.18 3-19 15.00 493.51 313.00 180.51 78.22 3-20 7.50 495.53 302.00 193.53 83.86 3-21 18.00 494.87 309.00 185.87 80.55 3-22 12.00 494.76 310.00 184.76 80.06 3-23 0.00 494.42 305.00 189.42 82.08 3-24 4.50 493.50 312.00 181.50 78.65 3-25 6.00 493.80 304.00 189.80 82.25 3-26 18.00 493.32 309.00 184.32 79.87 3-27 0.00 496.45 295.00 201.45 87.29 3-28 36.00 493,01 311.00 182.01 78.87 3-29 22.50 492.87 322.00 170.87 74.05 3-30 0.00 493.53 322.00 171.53 74.33 3-31 28.50 493.49 318.00 175.49 76.04 3-32 3.00 493.49 320.00 173.49 75.18 3-34 0.00 493.49 318.00 175.49 76.04 R-1 Wellborn Ele ---- 497.00 342.00 155.00 67.17 R-2 Flow Test ---- 497.00 311.00 186.00 80.60 SUMMARY OF I N FLOW S AND OUTFLOWS (+) INFLOWS INTO THE SYSTEM FROM SUPPLY NODES (-) OUTFLOWS FROM THE SYSTEM INTO SUPPLY NODES NODE FLOWRATE NODE NAME (gpm) TITLE R-1 1820.47 Wellborn Ele R-2 1035.03 Flow Test NET SYSTEM INFLOW = 2855.50 NET SYSTEM OUTFLOW = 0.00 NET SYSTEM DEMAND = 2855.50 ***** HYDRAULIC ANALYSIS COMPLETED ***** ENGINEER'S COST ESTIMATE �- — RME Consulting Engineers POST OFFICE BOX 9253 ME COLLEGE STATION,TEXAS 77842 Go.�u. OFF/FAX:� g OFF/FAX: (979)690-0329 E-mail: civil@rmengineer.com CD1-213-0304-E02 2 of 2 ENGINEER'S COST ESTIMATE RME Consulting Engineers POST OFFICE BOX 9253 MH COLLEGE STATION,TEXAS 77842 aGonsu/r(ny Eny j -t s OFF/FAX: (979)690-0329 E-mail: civil@rmengineer.com CD1-213-0304-E02 2 of 2 ME P.O.Box 9253,College Station,TX 77842 Off/Fax: (979)690-0329 C.onsc�/t(n9 Engineers email:civil@rmengineer.com October 11, 2007 David Loflin Texas Commission of Environmental Quality Water Supply Division MC 153 P.O. Box 13087 Austin, TX 78711 RE: A&M Super Storage @ Wellborn—College Station, TX TCEQ Exception Letter for Utility Improvements RME No. 213-0304 Mr. David Loflin: The above referenced project will install the following improvements within the distribution system of the Wellborn S.U.D.: ❖ Approximately 200 linear feet of 16"PVC (C-905, Class 235)water line; ❖ Applicable valves& fittings. Design and construction of these improvements will be in accordance with the latest Bryan/College Station Unified Water & Sewer Design Guideline Manual, Standard Details, and Specifications and Chapter 290 of the TCEQ Rules& Regulations. This quantity of water line is less than 10% of the total length of water line within the City's current distribution system. Therefore, an exception for plan review is being requested for this project and its water system improvements. Please call should you have any questions or require assistance. Sincerely, �' 1 \li _. gam;:E.OF11.*Ak • 7C RABON A7ETCALF Rabon A. Metcalf, P.E. rabon@rmengineer.comTI 9 8858 :Q 0.`:/CENS:G�(,/� xc: Development Services n SSS✓•NA • N.� City of College Statio . .. 1101 Texas Avenue South /1) 07 College Station,TX 77840 �� CD1-213-0304-L05 Page 1 of 1 PUBLIC WATER SYSTEM PLAN REVIEW SUBMITTAL FORM (Complete and Attach to Submittal Package) Date: October 11, 2007 TCEQ PWS Identification No.*: 0210016 CCN No. or Application No.**:11340 Water System Name: Wellborn S.U.D. Water System Owner: Wellborn S.U.D. Type of Entity: S.U.D. Address: P.O. Box 250,Wellborn,TX 77881 Phone: (979)690-9799 Responsible Official: Steven Cast Title: Manager County (system location) : Brazos County Subdivision Sec., Phase, Unit, etc. A&M Super Storage t Wellborn Mechanism & Source of Financing: Private Engineer: Rabon A. Metcalf, P.E. Registration Number: 88583 Firm Name: RME Consulting Engineers Phone: (979) 690-0329 Firm Address: P.O. Box 9253, College Station,TX 77842 Fax: (979)690-0329 * If no PWS Number exists,the owner must submit a business plan,if required, in accordance with§290.39(f)and(g). **If a required CCN number does not exist,an acceptable application to obtain a CCN number must be made before a project submittal can be technically reviewed. In addition, if a submittal is for a project located outside the CCN area,a CCN amendment application must be submitted before a project may be reviewed for construction approval. Please refer to 30 TAC Chapter 291 for additional information regarding CCNs. If this is a new(proposed)system, you must attach the following with this submittal: NOT APPLICABLE ❑ Attach a list of all water utilities within %2 mile of the proposed service area boundaries ❑ Copies of formal applications for service from each of the following ❑ any municipality if the system is within its ETJ; ❑ any district or other political subdivision whose corporate boundaries are within 1/2 mile of the proposed service area boundaries ❑ any other water service provider whose certificated service area boundary is within 1/2 mile of the proposed service area boundaries ❑ Documentation that all application requirements including payment of fees were complied with. ❑ Copies of written responses from each of the entities listed above. ❑ Business plan, if required by 30 TAC 290.39(f) & (g). The business plan financial requirements for non-community water systems must confirm capital availability to construct the system according to TCEQ requirements. This would consist of a balance sheet that shows liabilities as well as assets, not just a bank confirmation of a deposit account. Alternatively, if the project is being constructed with loan funds, then a loan commitment letter from the lender specific to that project will suffice. ❑ Justification for constructing a separate system (unless none of the entities listed above exist) ❑ Plans and specifications with an engineering report all sealed by design engineer. Type of Project(please check the appropriate boxes): ❑ Distribution System Modifications 0 Storage Capacity Modifications ❑ Well completion data on previously approved well 0 Water Well Construction, Proposed ❑ Pressure Maintenance Facilities Modifications 0 Proposed Innovative Process Study ❑ Disinfection Facilities or Other Modifications 0 Ground Water Treatment Plant, New ❑ Preliminary Engineering Report w/o plans 0 Surface Water Treatment Plant, New ❑ Modification of Surface Water Treatment Plant 0 Tex. Water Dev. Board Proj. No. 0 Other(PleaseExplain) IF THIS SUBMITTAL IS A REVISION OF PREVIOUSLY SUBMITTED PLANS, PLEASE ENTER THE ASSIGNED TCEQ LOG NUMBER: . Please call (512)239-6960 if you have questions regarding this form. Your cooperation will help us provide better service. Additional helpful information and rules are available at our website: http://www.tceq.state.tx.us/permitting/waterperm/ud/planrer7AN `�` �EOF1 :q I hereby certify that the above information is, to the best of my knowledge, true an r f �'\ •.0It k- • • tft Rabon A. Metcalf, P.E. October 11, 2007 Printed Engineer's Name Date /, .se ' • 4ist.,��� ....;®.•�\� Revised 9/12/02 Box 9253,College Station,TX 77842 e...___ g- P.O. Off/Fax (979)690-0329 �`...... /,,� Eny/neers email: civil@rmengineer.com October 11, 2007 Development Services City of College Station 1101 Texas Avenue South College Station, TX 77842 RE: A&M Super Storage @ Wellborn—Acknowledgement of City Standards College Station E.T.J.,Brazos County,TX RME No. 202-0316 To Whom it May Concern: The purpose of this letter is to acknowledge that the construction plans for the sanitary sewer improvements, for the above referenced project, to the best of my knowledge, do not deviate from the latest B/CS Design Guideline Manual. I also acknowledge, to the best of my knowledge that the details provided in the construction plans are in accordance with the B/CS Standard Details. Please do not hesitate to call if you have any questions. Sincerely, x,`.01°*®® ..011111w lidurom. OFTF \ . Rabon A. Metcalf,P.E` 0RABON A. METC. \+ rabon@rmengineer.com 4 a i.. 88583 �7 � `blli vl 9oc` iCENS�.�'�4�4 k.q•. ::•NGS_/ ONAL E `.i CD1-213-0304-L04 Page 1 of 1